SPECIFICATIONS

GENERATOR SPECIFICATIONS

RP25

KILOWATT

20 kW

KILOVOLT-AMPS (.8 PF)25 kVA
AMPERAGE

277/480 VOLT 3 PHASE 30 AMPS*
120/240 VOLT 3 PHASE 60 AMPS*
120/208 VOLT 3 PHASE 69 AMPS*
120/240 VOLT 1 PHASE 70 AMPS**

*Based on .8 power factor
**Single Phase is limited by the circuit breaker to 150
Amps on the full power terminal block - The additional
amperage is available through receptacles.

Derate 3% per 1000 feet (305 meters) between 300 feet
(90 meters) and 7,500 feet (2,286 meters) above sea
level. Contact the factory for rating data for operation in
altitudes above 7,500 feet (2,286 meters).

For prime power application (24/7) derate all output rating
by 10%

GENERATOR RESISTANCE

RP25

Generator Make

Stamford

Generator Model

BCI184F

Generator Winding

#311

Voltage Regulator

SX460

Main Stator

0.13 ohms

Main Rotor

0.74 ohms

Exciter Stator

22 ohms

Exciter Rotor

0.23 ohms

ENGINE SPECIFICATIONS

See Iveco Operation and Maintenance Manual for com-
plete engine specifications.

TRAILER/HOUSING

RP25

Capacity

3500 lb.

Fuel Capacity

45 Gallons

Axles

Single

Hitch Height

Adjustable

Tires

P225/75R-15

Tire Pressure

35 psi

Sound Attenuated

ULTRA QUIET

Housing

Housing Standard

PREPARATION

NOTE: This booklet covers the entire unit, EXCEPT THE
ENGINE. See the engine manufacturer’s operator manual

for specific maintenance and care information regarding
the engine. Read ALL instructions in the manuals pro-
vided before attempting to operate the generator set.

UNPACKING

When receiving the unit, be sure to inspect it carefully for
freight loss or damage. Check the nameplate to be sure it
is what you ordered (proper kW, voltage, fuel, etc.). If you
have questions, contact your local authorized dealer. If
you see evidence of loss or damage at the time of deliv-
ery, have the driver sign and describe the loss or damage
in the “memo of loss or damage” section on the freight
bill. Then contact the carrier to get instructions on filing a
claim.

When loss or damage is discovered after the equipment
is delivered, but not seen at the time of delivery, it is
referred to as “concealed damage.” Separate any dam-
aged material and contact the carrier for proper proce-
dures to file a “concealed damage” claim.

OIL REQUIREMENTS

This engine was filled at the factory. Before starting
check the oil level and ensure it is full. If not, refill to the
proper level. See engine manual for proper grade of oil.

OIL QUANTITY

US Qt.

Liters

RP55

7

6.6

FUEL REQUIREMENTS

See your engine operator's manual for complete type and
fuel grade information.

WARNING -NO BIODIESEL

Filling the Fuel Tank

Standard Trailer - The standard trailer is equipped with a
single 45 gallon fuel tank. Use caution when filling the
tank so as not to overflow the tank into the trailer.

WARNING PERSONAL DANGER
Never refuel a running engine. Always stop the engine
and allow to cool before refueling.

Never allow the fuel tank to run completely empty, as air
may enter the fuel system making it necessary to bleed
the engine when restarting.

COOLANT REQUIREMENTS

The cooling system of this engine has been filled at the
factory with a 50% water and 50% ethylene-glycol
antifreeze and the proper amount of supplemental coolant
additives. This mixture provides engine protection to -37
degrees F.