Specifications, Preparation – Winco RP25/A User Manual
Page 4
Page 2
60706-201
8190-00
SPECIFICATIONS
GENERATOR SPECIFICATIONS
RP25
KILOWATT
20 kW
KILOVOLT-AMPS (.8 PF)25 kVA
AMPERAGE
277/480 VOLT 3 PHASE 30 AMPS*
120/240 VOLT 3 PHASE 60 AMPS*
120/208 VOLT 3 PHASE 69 AMPS*
120/240 VOLT 1 PHASE 70 AMPS**
*Based on .8 power factor
**Single Phase is limited by the circuit breaker to 150
Amps on the full power terminal block - The additional
amperage is available through receptacles.
Derate 3% per 1000 feet (305 meters) between 300 feet
(90 meters) and 7,500 feet (2,286 meters) above sea
level. Contact the factory for rating data for operation in
altitudes above 7,500 feet (2,286 meters).
For prime power application (24/7) derate all output rating
by 10%
GENERATOR RESISTANCE
RP25
Generator Make
Stamford
Generator Model
BCI184F
Generator Winding
#311
Voltage Regulator
SX460
Main Stator
0.13 ohms
Main Rotor
0.74 ohms
Exciter Stator
22 ohms
Exciter Rotor
0.23 ohms
ENGINE SPECIFICATIONS
See Iveco Operation and Maintenance Manual for com-
plete engine specifications.
TRAILER/HOUSING
RP25
Capacity
3500 lb.
Fuel Capacity
45 Gallons
Axles
Single
Hitch Height
Adjustable
Tires
P225/75R-15
Tire Pressure
35 psi
Sound Attenuated
ULTRA QUIET
Housing
Housing Standard
PREPARATION
NOTE: This booklet covers the entire unit, EXCEPT THE
ENGINE. See the engine manufacturer’s operator manual
for specific maintenance and care information regarding
the engine. Read ALL instructions in the manuals pro-
vided before attempting to operate the generator set.
UNPACKING
When receiving the unit, be sure to inspect it carefully for
freight loss or damage. Check the nameplate to be sure it
is what you ordered (proper kW, voltage, fuel, etc.). If you
have questions, contact your local authorized dealer. If
you see evidence of loss or damage at the time of deliv-
ery, have the driver sign and describe the loss or damage
in the “memo of loss or damage” section on the freight
bill. Then contact the carrier to get instructions on filing a
claim.
When loss or damage is discovered after the equipment
is delivered, but not seen at the time of delivery, it is
referred to as “concealed damage.” Separate any dam-
aged material and contact the carrier for proper proce-
dures to file a “concealed damage” claim.
OIL REQUIREMENTS
This engine was filled at the factory. Before starting
check the oil level and ensure it is full. If not, refill to the
proper level. See engine manual for proper grade of oil.
OIL QUANTITY
US Qt.
Liters
RP55
7
6.6
FUEL REQUIREMENTS
See your engine operator's manual for complete type and
fuel grade information.
WARNING -NO BIODIESEL
Filling the Fuel Tank
Standard Trailer - The standard trailer is equipped with a
single 45 gallon fuel tank. Use caution when filling the
tank so as not to overflow the tank into the trailer.
WARNING PERSONAL DANGER
Never refuel a running engine. Always stop the engine
and allow to cool before refueling.
Never allow the fuel tank to run completely empty, as air
may enter the fuel system making it necessary to bleed
the engine when restarting.
COOLANT REQUIREMENTS
The cooling system of this engine has been filled at the
factory with a 50% water and 50% ethylene-glycol
antifreeze and the proper amount of supplemental coolant
additives. This mixture provides engine protection to -37
degrees F.