2 PROPORTIONNAL OUTPUT

Fig.4: Wiring diagram with two analog outputs

1 PROPORTIONNAL AND 1 TRANSMITTER OUTPUT

Fig.5: Wiring diagram with one analog and one transmitter output

APPLICATION EXAMPLE:

Steam humidification system controlled by a 0 to 10 Vdc valve wired to output #1. Remote humidity display using 0 to 5 Vdc signal is wired to
output #2. The humidity sensor is located in the return air duct. A proportional high limit humidity sensor is installed in the supply duct. An
outdoor temperature sensor is installed in the fresh air duct.

Humidistat model number: H270-69-13-10-31

Fig.6: Application example

6

COMMON

TEMP. SENSOR

OUTDOOR

SENSOR

HIGH LIMIT

INPUT

MAIN SENSOR

+10 Vdc

9

10

8

7

OUTPUT #1

TRANSMITTER

0 to 10 Vdc

0 to 5 Vdc

OUTPUT #2

24 Vac

0 to 10 Vdc

4

5

3

24 Vac

2

1

FOR CONTROL

HUMIDITY SENSOR

RED

BLACK

WHITE

DDC SYSTEM

ELECTRONIC MOTOR
or "SCR"

-

+

or METER

-

+

6

COMMON

N/A

N/A

INPUT

MAIN SENSOR

+10 Vdc

9

10

7

8

OUTPUT #1

0 to 10 Vdc

OUTPUT #2

24 Vac

0 to 10 Vdc

4

5

3

24 Vac

2

1

FOR CONTROL

HUMIDITY SENSOR

RED

BLACK

WHITE

ELECTRONIC MOTOR

ELECTRONIC MOTOR
or "SCR"

-

+

or "SCR"

-

+