beautypg.com

Viconics H100 User Manual

Page 3

background image

Viconics Electronics Inc. 9245, Langelier Blvd, St-Leonard, Quebec, Canada H1P 3K9

www.viconics.com

[email protected]

10/31/02 LIT-H100X-E02 H100.doc

3

1.275" [32mm]

Cover

1.275" [32mm]

2.8" [71mm]

2.8" [71mm]

3.275" [83mm]

Wiring from top

Security screw

Base

Wiring from back

2.0" [50.8mm]

3.77" [95.8mm]

Cover

0.9" [22.8mm]

4.5" [114mm]

SPECIFICATIONS

Operating Conditions: 5 °C to 50 °C ( 32 °F to 122 °F )

0% to 95% R.H. non-condensing

•Sensor: 0% to 100% R.H. (see Note 1.)

Resolution:

0.5 %

Repeatability:

0.5 %

Accuracy and sensor interchangeability:

± 2 % R.H. from 0 to 100 % R.H.

Range:

0 % to 100 % R.H. for 5 to 50 °C
(41 °F to 122 °F )

Temperature effect:

0.05 % / °F

Outputs:

0 to 5 VDC into 1K

Ω resistance min.

0 to 10 VDC into 2K

Ω resistance min.

Power:

24 VAC -15%, +10%; 50/60 Hz; 2 VA

Base & casing: Off-white; self extinguishing

ABS plastic

Note 1. Humidity sensor: Solid state humidity sensor.
Suitable for normal, clean air. Not to be used in
corrosive or harmful environment.

WIRING

Fig.2: Wiring diagram

DIMENSIONS

Note: Specifications and equipment are subject to change without prior notice.

Fig.3: Dimension drawing

TABLE 3: SENSOR
CHARACTERISTICS

Voltage between black and white
wire, terminals #6 and #7

HUMIDITY

SENSOR OUTPUT

0 %

1.05 V

5 %

1.19 V

10 %

1.34 V

15 %

1.48 V

20 %

1.63 V

25 %

1.77 V

30 %

1.92 V

35 %

2.06 V

40 %

2.20 V

45 %

2.35 V

50 %

2.49 V

55 %

2.64 V

60 %

2.78 V

65 %

2.93 V

70 %

3.07 V

75 %

3.21 V

80 %

3.36 V

85 %

3.50 V

90 %

3.65 V

95 %

3.79 V

100 %

3.94 V

WHITE

MAIN SENSOR

10

+10 Vdc

N/A

N/A

INPUT

FOR CONTROL

RED

8

9

7

24 Vac

COMMON

N/A

SIGNAL OUTPUT

0 to 10 Vdc

TRANSMITTER

N/A

0 to 5 Vdc

HUMIDITY SENSOR

BLACK

24 Vac

5
6

4

2

3

1

DDC SYSTEM
or METER

-

+