Characteristics of changeover sensor 47 K

Temperature °F

Temperature °C

Sensor resistance

150.0 °F

65.6 °C

9.610 Kohm

140.0 °F

60.0 °C

11.700 Kohm

130.0 °F

54.4 °C

14.342 Kohm

120.0 °F

48.9 °C

17.682 Kohm

110.0 °F

43.3 °C

21.940 Kohm

100.0 °F

37.8 °C

27.412 Kohm

90.0 °F

32.2 °C

34.483 Kohm

80.0 °F

26.7 °C

43.704 Kohm

70.0 °F

21.1 °C

55.834 Kohm

60.0 °F

15.6 °C

71.866 Kohm

50.0 °F

10.0 °C

93.340 Kohm

40.0 °F

4.4 °C

122.298 Kohm

THERMOSTAT INSTALLATION

Important.
Electronic controllers require special care for wiring
and startup. To avoid problems, carefully follow the
procedures below.

Be sure to have all the literature on hand for all components
installed: controller, actuators, relay, etc...

Look at the wiring diagrams, and study them carefully. Be
sure that you understand how the system is supposed to
work.

Make the wiring according to the wiring diagrams. Respect
polarity for power terminals # 3 & # 4 between multiple
controllers if the same transformer is used.

Remove security screw on left side of thermostat cover.

Open up by pulling on the bottom side of thermostat.

A) Location:

1- Shouldn’t be installed on outside wall.
2- Must be installed away from any heat source.
3- Shouldn’t be affected by direct sun radiation.
4- Nothing must restrain vertical air circulation to the

thermostat.

B) Installation:

1- Pull out cables 6” out of the wall.
2- Wall surface must be flat and clean.
3- Separate the thermostat and the base by pulling

the cover by the bottom (same as the security
screw.)

4- Insert cable in the central hole of the base.
5- Align the base and mark the location of the two

mounting holes on the wall. Install proper side of
base up.

6- Install shields in the wall.
7- Insert screws in mounting holes on each side of the

base. DO NOT OVERTIGHTEN!

8- Strip each wire 1/4 inch.
9- Insert each wire according to wiring diagram.
10- Reinstall the cover ( top side first ) and gently push

back extra wire length in the hole in the wall.

11- Install security screw.

CONTROL CURVES AND SEQUENCE

Temperature increase

Heating mode

changeover
input active

50 %

Opened

100%

Closed

0%

SETPOINT DIAL

Device

opened

Device closed

Cooling mode

Device

opened