Viconics C1011 User Manual
Electronic thermostats c1011
1
ELECTRONIC THERMOSTATS
C1011
• One floating output
• Supply air temperature auto changeover input
DESCRIPTION
The C1011 series thermostats are microcomputer-based,
proportional and integral (PI) devices with one floating
(incremental) output. It can be used with most controlled
devices in the HVAC industry that are compatible with this
signal. Typical applications would be to control a floating
VAV or valve actuator. The thermostats also contain a berg
jumper for the actuator stroke time from full open to full
close.
Type of
output
In cooling
In heating
Modulating
floating
Modulating devices
Floating damper
actuator
Floating valve
actuator
Modulating devices
Floating damper
actuator
Floating valve
actuator
SPECIFICATIONS
Operating Conditions:
0 °C to 50 °C ( 32 °F to 122 °F )
0% to 95% R.H. non-condensing
Sensor:
Local 47 K NTC thermistor
Resolution:
± 0.1 °C ( ± 0.2 °F )
Control accuracy:
± 0.2 ° C ( ± 0.4 °F ) ( calibrated )
Ranges:
10 °C to 32 °C ( 50 °F to 90 °F )
Proportional band for room
temperature control:
1.8°C ( 3.2°F )
Floating output:
Non isolated triacs: 30 Vac, ½ A max.
Power:
24 Vac -15%, +10% 50/60 Hz; 2 VA
DIMENSIONS
HOW TO ORDER
C1011
-
↓
00C = °C scale
↓
00F = °F scale
Notes:
• Order changeover sensor separately.
• Vertical mounting is standard.
MODULATING FLOATING OUTPUT
This output is designed to give true PI modulation out of
floating actuator for VAV dampers and valves.
The thermostat is designed for operation with actuators that
have a running time of 1.5 to 2.5 minutes for the full open /
close stroke time.
The output is normally cooling but can be reversed to
heating mode with 2 different methods:
• Auto changeover to heating mode with a supply
sensor.
A remote supply sensor can be used for each thermostat.
Supply temperature
> 78°F (26°C) = heating mode
Supply temperature
< 75°F (24°C) = cooling mode
Hysterisys is 3°F (2°C)
• Auto changeover to heating mode with a dry contact.
A closed contact on the changeover input will change
operation of the floating output to heating mode.
Open contact = cooling mode
Closed contact = heating mode
32 mm
( 71 mm )
2.8"
1.275"
( 83 mm )
3.275"
SECURITY SCREW
OR FROM BACK
FROM TOP
WIRING
BASE
( 114 mm )
4.5"
50
70
60
90
80
F