Viconics C1011 User Manual

Electronic thermostats c1011

background image

1

ELECTRONIC THERMOSTATS

C1011

• One floating output

• Supply air temperature auto changeover input

DESCRIPTION

The C1011 series thermostats are microcomputer-based,
proportional and integral (PI) devices with one floating
(incremental) output. It can be used with most controlled
devices in the HVAC industry that are compatible with this
signal. Typical applications would be to control a floating
VAV or valve actuator. The thermostats also contain a berg
jumper for the actuator stroke time from full open to full
close.

Type of

output

In cooling

In heating

Modulating

floating

Modulating devices

Floating damper

actuator

Floating valve

actuator

Modulating devices

Floating damper

actuator

Floating valve

actuator

SPECIFICATIONS

Operating Conditions:

0 °C to 50 °C ( 32 °F to 122 °F )
0% to 95% R.H. non-condensing

Sensor:

Local 47 K NTC thermistor

Resolution:

± 0.1 °C ( ± 0.2 °F )

Control accuracy:

± 0.2 ° C ( ± 0.4 °F ) ( calibrated )

Ranges:

10 °C to 32 °C ( 50 °F to 90 °F )

Proportional band for room

temperature control:

1.8°C ( 3.2°F )

Floating output:

Non isolated triacs: 30 Vac, ½ A max.

Power:

24 Vac -15%, +10% 50/60 Hz; 2 VA

DIMENSIONS

HOW TO ORDER

C1011

-


00C = °C scale

00F = °F scale

Notes:
• Order changeover sensor separately.
• Vertical mounting is standard.

MODULATING FLOATING OUTPUT

This output is designed to give true PI modulation out of
floating actuator for VAV dampers and valves.

The thermostat is designed for operation with actuators that
have a running time of 1.5 to 2.5 minutes for the full open /
close stroke time.

The output is normally cooling but can be reversed to
heating mode with 2 different methods:

Auto changeover to heating mode with a supply

sensor.

A remote supply sensor can be used for each thermostat.
Supply temperature

> 78°F (26°C) = heating mode

Supply temperature

< 75°F (24°C) = cooling mode

Hysterisys is 3°F (2°C)

Auto changeover to heating mode with a dry contact.

A closed contact on the changeover input will change
operation of the floating output to heating mode.
Open contact = cooling mode
Closed contact = heating mode

32 mm

( 71 mm )

2.8"

1.275"

( 83 mm )

3.275"

SECURITY SCREW

OR FROM BACK

FROM TOP

WIRING

BASE

( 114 mm )

4.5"