Field controls – Slant/Fin TRDV Series Venting User Manual
Page 13
TRDV SERIES
13
APPLIANCE ADAPTER INSTALLATION:
1. Apply a bead of sealant to appliance collar approx. 1” from
end of collar (Figure 20).
2. Remove all oil and grease from the inside of the appliance
adapter, and apply a bead of sealant to inside of adapter ?”
from end (Figure 20).
3. With a twisting motion, assemble the appliance adapter onto t
he appliance collar.
4. Using a mallet and block of wood, drive the adapter onto the
appliance collar, using care to avoid damaging the appliance
collar or the adapter (Figure 21).
5. Assemble adapter clamp halves using the supplied 5/16” bolts
and square nuts, and install the appliance clamp onto the
adapter and tighten securely (Figure 20).
6. Install the supplied self-drilling, self-tapping anchoring screws
through the 4 holes in the appliance clamp into the appliance
collar (Figure 21). No pilot hole is required.
7. Apply sealant to the end of the adapter and anchoring screws.
(Figure 21).
8. After testing and burner adjustments have been made, apply
sealant to the supplied 3/8” sampling port plug screw and
install the screw in the sampling port (Figure 21).
9. Maintain the following clearances to combustibles. If the
appliance collar is within 18" of combustible material, wrap
minimum 1-1/2" ceramic insulation (installer-supplied) around
the exposed portion of the termination inner pipe and
appliance adapter (Figure 25).
Figure 19
Figure 20
Figure 21
FIELD CONTROLS
REFER TO PAGE 8 FOR VACUUM RELIEF VALVE CONNECTIONS AND VENT SYSTEM PART NUMBERS