EH-M3-40 Boiler Operation and Installation Instructions
Field Entry
Low Temperature System
Note
MODE
4 or 5
4 = Parallel Piping, 5 = Primary/Secondary Piping
STGMODE
PID
P
P
BOIL TARGET
180
180
180
This is for DHW setpoint demand - if used
OUTDR START
70
70
70
OUTDR DSGN
-10
-10
-10
May be -20 or -30F depending on area design temp.
BOIL START
70
70
70
This is used in the calculation of slope
BOIL DSGN
180
180
130
Radiant - 130 Wet, 140 or 150F for Dry system
BOIL OUT MAX
200
200
150
Default 200 - Use "FACTORY" Dip Switch to Adjust
Can be set 10F over BOIL DSGN
BOIL MAX
170
170
130
Default 180 - Use "FACTORY" Dip Switch to Adjust
Set same as BOIL DSGN
BOIL MIN
140
140
80
Default 140 - Use "FACTORY" Dip Switch to Adjust
Note:Some heating equipment may require a
minimum water temperature - ie fan coils
DLY
Not valid for Electric Boiler application
BOIL MASS
1
N/A
N/A
STG DLY
Au if PID in STGMODE
N/A
N/A
Minimum time between firing stages
DIFF
Au if PID in STGMODE
2
2
On or off of contact = 1/2 differential around target temp
STG DIFF
4
4
Temperature drop at which next stage turns on
ON DLY
1:00
1:00
Time before turning on next stage
OFF DLY
0:30
0:30
Time before turning off next stage
MIN ON
0:30
0:30
Minimum time stage is on before allowed to go off
MIN OFF
0:30
0:30
Minimum time stage is off before allowed to come on
PUMP DELAY
Off
Off
Off
WWSD
0 F
Caution:
"Factory" position on dip switch has to be returned to "Installer" position to prevent unauthorized changes to
Factory settings.
F or C
Field Entry Example for Mode 4 or Mode 5
Basic Monitron II and Minitron M3 Setup
Set the "MODE" to 1 or 2 if an outdoor Sensor is not used (1 = parallel piping, 2 = primary/secondary piping)
Baseboard System
4 or 5
no entry
65