BOILER "A" "B" "C" "D"
MODEL
LX-90 6 3/4 3 3/8 2 3/4 16 1/4
LX-120 6 5/8 3 3/8 2 16 1/4
LX 150
6 3/8
3 3/4
2 3/4
19
33
35
22
LEFT SIDE FRONT RIGHT SIDE
5
"D"
"A"
"B"
"C"
Lynx
2
RATINGS AND DIMENSIONS
Figure 1. Dimensions data
SPECIFICATIONS
BOILER MODEL
LX-90
LX-120
LX-150
Input Rate, Btu/Hr
Max.
Min.
90,000
25,000
120,000
30,000
150,000
37,500
Water Piping Connection
1" NPT (Male)
Gas Piping Connection
1/2" NPT (Female)
Vent Connection
3" Nominal ID Pipe PVC, CPVC, Polypropylene
(solid or flexible) or SS. SEE WARNING
Air Intake Connection
3" Nominal ID PVC or CPVC
Gas Orifice Size for Natural Gas
No Orifice Used
Gas Orifice Size for Propane
0.1900"
Code # C
0.2025"
Code # A
0.2200"
Code # E
Boiler Water Volume
Gal.
0.4
0.6
1.1
Weight of Boiler (Uncrated)
Lbs.
118
125
140
WARNING:
1. Use of cellular core PVC and CPVC or Radel for venting system is NOT allowed
2. Thermal insulation on non-metallic vent pipe and fittings is NOT allowed.
BOILER "A" "B" "C" "D"
MODEL
LX-90 6 3/4 3 3/8 2 3/4 16 1/4
LX-120 6 5/8 3 3/8 2 16 1/4
LX-150 6 3/8 3 3/4 2 3/4 19