Slant/Fin EC-20 Installation User Manual
Page 2

EUTECTIC EC-20
2
Maximum operating pressure 60 psi.
All boilers hydrostatically tested — A.S.M.E.
* For forced hot water heating systems where the boiler and all piping are
located within the area to be heated, the boiler may be selected on the basis
of D.O.E. capacity output. The net AHRI output ratings shown are based on
an allowance for piping and pickup of 1.15 (water). D.O.E. capacity output is
divided by the allowance to obtain net rating. The Slant/Fin Technical Service
department should be consulted before selecting a boiler for unusual piping
and pickup requirements such as intermittent system operation, extensive
piping, etc.
† Ratings apply to the use of light oil at 140,000 Btu per gallon and apply only
when burner models listed on page 12 of this manual are used, and are
properly adjusted to produce 13% CO2.
# All dimensions subject to normal manufacturing tolerance.
NOTE: All boilers under 300,000 Btuh (87.9 kw) input are tested and rated for
capacity under the U.S. Department of Energy (D.O.E.) Test Procedures for
Boilers.
TABLE 1: Ratings and Dimensions
EC-25
1.55 217,000
190
165
6 x 15 86.5
N/A
32-9/16
35-3/8
46-3/8
6
20
2
EC-26
1.90 266,000
232
202
7 x 15 86.5
N/A
37-9/16
40-3/8
51-3/8
7
25
2
EC-27
2.25 315,000
269
234
7 x 15
N/A
85.3
42-9/16
45-3/8
56-3/8
7
30
2
EC-28
2.50 350,000
298
259
7 x 15
N/A
85.3
47-9/16
50-3/8
61-3/8
7
35
2
BOILER
MODEL
NO.
GPH
BTUH
AHRI
BURNER
CAPACITY
OIL INPUT † §
D.O.E.
HEATING
CAPACITY
MBH *
WATER
APPROX.
OVERALL
LENGTH
“A”
THERMAL
EFF. (%)
AHRI
WATER
NET
RATING
MBH *
AHRI
CHIMNEY SIZE
DIMENSIONS (inches) #
I.D. ROUND
X HEIGHT
(in x ft)
AFUE
%
BOILER
LENGTH
“B”
BOILER
LENGTH
“C”
FLUE
DIA.
“D”
DISTANCE
BETWEEN
LEGS
“E”
FLUE
OUTLET
LENGTH
“F”
Figure 1: Dimensions
Air Eliminator
as per Manufacturer
Specifications
To Circ. (s)
and Zones
1-1/2”
NPT
Supply
Automatic
Air Vent
Suppy Pipe Mounted
Tridicator
A
1-1/2”
NPT
Return
3/4”
NPT
Drain
D