4 lightning protection, 5 keypads – Potter PFC-7500 Series User Manual
Page 8
4
3.3
PFC-7500 Wiring Diagram
The PFC-7500 system below shows some of the accessory devices for use in various applications.
AC
1
3
+B
5
BELL
6
SMK
11
Z1A+
7
RED
8
YEL
9
GRN
10
BLK
2
AC
4
-B
12
Z1A-
13
Z1B+
14
Z1B-
15
Z2+
16
Z2-
17
Z3+
18
Z3-
19
Z4+
20
Z4-
21
Z5+
22
Z5-
N/O
N/C COM
N/O
N/C COM
J11
1
2
3
4
J12
OUTPUT
2
OUTPUT
1
MAIN BACKUP
Telephone
Connections
J4
J5
Silence/Reset
Header
J13
Bell
Monitor
J14
Silence/Reset
Button
Silence/Reset
Push for 1 Second
Panel
Reset
J10 Trouble Annunciator Header
Relay Sockets for Optional
Form C Outputs on J11
RE
D
BL
AC
K
G
RE
EN
Up to 500mA auxiliary current at 12 VDC from terminal 7
BL
AC
K
YE
LL
O
W
RE
D
GROUND
Cold Water Pipe
E arth Ground
Output Header J11
Two Form C (SPDT) Outputs.
Zo
ne
2
Output Header J12
Four Open Collector Outputs.
50mA at 30 VDC resistive
Zone 1
M
M
Direct connect to
unswitched 120 VAC 60 Hz
Secondary Power Supply
12 VDC
1.2 Amps Max. charging current.
Zone 5
Output 1 Output 2
W
W
Zo
ne
3
S
S
TAM
Trouble
Annunciator
Module
Model WLT
16.5 VAC 40VA
wire-in transformer
3.3k
Ohm
EOLR
Zo
ne
3
H
S
Keypad
Model RA-7630
For sprinkler supervision,
Normally Open devices
must be used.
Zone 2
3.3k Ohm
Zone 4
3.3k Ohm
Zone 3
3.3k Ohm
Al outputs must be
connected to devices
located within the same
room as the panel.
Heat detectors, pull stations, or any other contact devices listed
for Fire Protective Signaling can be connected to zones 1 to 5.
Zones 2 to 5 compatibility identifier: A
Maximum operating range: 8.8 to 14.2 VDC.
S
S
S
S
S
S
S
S
S
S
S
S
S
= Supervised Circuit
5 Zone LED Keypads
Keypad
Model RA-7692
30mA at 8 to 16 VDC.
63mA at 8.5 to 14 VDC
POWER
TROUBLE
ALARM
COMMAND
1
2
3
4
5
6
7
8
9
0
ABC
DEF
GHI
JKL
MNO
PQR
STU
VWX
YX
ENABLE
SILENCE
RESET
TEST
DRILL
Fire Command Center
S
S
S
S
S
S
POWER LIMITED
All circuits on the Model PFC-7500 comply
with the requirements for inherent power
limitation and are Class 2 except the
red battery wire.
WARNING
THIS UNIT MAY BE PROGRAMMED TO USE AN ALARM
VERIFICATION FEATURE THAT RESULTS IN DELAY OF THE SYSTEM
ALARM SIGNAL FROM THE INDICATED CIRCUITS. THE TOTAL
DELAY (CONTROL UNIT PLUS SMOKE DETECTORS) SHALL NOT
EXCEED 60 SECONDS. NO OTHER SMOKE DETECTORS SHALL BE
CONNECTED TO THESE CIRCUITS UNLESS APPROVED BY THE
LOCAL AUTHORITY HAVING JURISDICTION.
All zones are supervised
USE MARKING
Commercial Protected Premises
Control Unit
TYPES OF SERVICE
Central Station DACT, Remote Station Signaling Service, Suitable for
manual fire alarm, automatic fire alarm, sprinkler supervisory or
waterflow alarm.
Figure 2: PFC-7500 Wiring Diagram
3.4
Lightning Protection
Metal Oxide Varistors and Transient Voltage Suppressors on the panel help protect against voltage surges on
input and output circuits of the PFC-7500 Series panels. Additional surge protection is available by installing the
Lightning Suppressors.
3.5
Keypads
You can connect the Models RA-7630 or RA-7692 keypads to the 4-wire keypad bus provided by the panel on terminals
7, 8, 9, and 10. Do not use shielded wire for the keypad bus.