beautypg.com

System components, 1 description – Potter PFC-7500 Series User Manual

Page 7

background image

3

3.1

Description

A basic PFC-7500 Series system is made up of the alarm panel with built-in communicator, an enclosure, a 16.5 VAC

wire-in transformer, and a 12 VDC 7.0 Ah battery. You can add up to two alphanumeric keypads and one or more LED

keypads to the panel and also connect control and annunciating devices to the panel Form C and annunciator outputs.

Refer to the Power Requirements section in this guide when calculating power requirements.

3.2

PFC-7501 Wiring Diagram

The PFC-7501 system below shows some of the accessory devices for use in various applications.

Panel Reset

RE

D

BL

AC

K

GR

EE

N

Keypad bus

22 gauge min.

BL

AC

K

YE

LL

O

W

RE

D

Cold Water Pipe

Earth Ground

Output Header J11

Two Form C (SPDT) Outputs.

Zo

ne

2

AC

1

2

3

4

7

8

10 11 12 13

14 15 16

AC

B+

B-

9

RED YEL GRN BLK

Z1B-

Z2 -

Z2+

1

2

3

4

J12

Z1A- Z1B+

Z1A+

MODEL 7500

MAIN BACKUP

J11

N/C COM N/O N/C COM N/ O

Output Header J12

Four Open Collector Outputs.

50mA at 30 VDC resistive

Relay Sockets for Optional

Form C Outputs on J11

Requires Form C Relays

Telephone Connections

Zone 1

J10 Trouble Annunciator Header

S

S

Direct connect to

unswitched 120 VAC 60 Hz

Secondary Power Supply

12 VDC

1.2 Amps max. charging current.

Up to 500mA auxiliary

current at 12 VDC from

Terminal 7.

5 Zone LED Keypads

5

6

BELL SM K

Zone 4

Zone 5

Bell Circuit

Power

Supervision

Relay

(if code requires)

Keypad

Model RA-7692

30mA at 8 to 16 VDC

Expander

Model ZA714/ZA715

7mA at 12 VDC

+

3.3k

EOLR

+

Smoke

Detector

RED

BLACK

GROUND

Output 1

Output 2

OU

TP

UT

1

OU

TP

UT

2

SILENCE/RESET

PUSH FOR ONE SECOND

Silence/Reset

Button

Silence/Reset

Header

17 18

Z3 -

Z3+

19 20

Z4 -

Z4+

21 22

Z5 -

Z5+

W

W

Up to 100mA of current is available for

All zones are supervised

4-wire smoke detectors from terminal 6.

Bell Monitor

Zo

ne

3

S

S

-

-

J13

Smoke

Detector

3.3k

EOLR

J14

TAM

Trouble

Annunciator

Module

Model 320

16.5 VAC 40V A

wire-in transformer

3.3k

EOLR

Keypad

Model RA-7630

63mA at 8.5 to 14 VDC

POWER

TROUBLE

ALARM

COMMAND

1

2

3

4

5

6

7

8

9

0

ABC

DEF

GHI

JKL

MNO

PQR

STU

VWX

YX

ENABLE

SILENCE

RESET

TEST

DRILL

Fire Command Center

C1

C4

U1

U2

CR3

TXD

J1

R

E

D

Tens Ones

.6 Amps at 12 VDC

S

S

S

S

S

S

POWER LIMITED

All circuits on the Model PFC-7501 comply

with the requirements for inherent power

limitation and are Class 2 except the

red battery wire.

WARNING

THIS UNIT MAY BE PROGRAMMED TO USE AN ALARM

VERIFICATION FEATURE THAT RESULTS IN DELAY OF THE SYSTEM

ALARM SIGNAL FROM THE INDICATED CIRCUITS. THE TOTAL

DELAY (CONTROL UNIT PLUS SMOKE DETECTORS) SHALL NOT

EXCEED 60 SECONDS. NO OTHER SMOKE DETECTORS SHALL BE

CONNECTED TO THESE CIRCUITS UNLESS APPROVED BY THE

LOCAL AUTHORITY HAVING JURISDICTION.

S

S

S

S

S

S S

S

S

S

S

S

S

S

S

S

USE MARKING

Commercial Protected

Premises Control Unit

TYPES OF SERVICE

Central Station DACT, Remote Station Signaling Service, Suitable for manual fire

alarm, automatic fire alarm, sprinkler supervisory or waterflow alarm.

Figure 1: PFC-7501 Wiring Diagram

System Components