Т³гж 12, Troubleshooting tips, Solution – Perfect Aire PAC5200 User Manual
Page 13: Problem
12
Before calling for service, review this list. It may save you time and expense. This list includes common
occurrences that are not the result of defective workmanship or materials in this appliance.
Solution
Air conditioner
does not start
Wall plug disconnected. Push plug firmly into direct wall outlet.
House fuse blown or circuit breaker tripped. Replace fuse with time delay type or reset circuit breaker.
Selector Control in OFF position. Turn selector to the desired FAN or COOL setting.
TROUBLESHOOTING TIPS
Problem
Air from unit does
not feel cold
enough
Thermostat set too warm. Set thermostat to colder temperature.
Turn selector to a higher COOL position.
Room temperature below 62 F(17 C). Cooling may not occur until room temperature rises above 62 F(17 C).
Thermostat set too cold for night-time cooling. To defrost the coil, set selector to a FAN position.
Then, set thermostat to a warmer position.
Temperature sensing tube touching cold coil, located behind air filter. Straighten tube away from coil.
Air filter may be dirty. Clean filter. Refer to Care and Cleaning section. To defrost, set selector to FAN.
Dirty air filter- air restricted. Clean air filter. Refer to Care and Cleaning section.
Unit recently turned on in hot room. Allow additional time to remove Stored heat from walls, ceiling, floor and furniture.
Unit turned off by moving thermostat to a higher number and then immediately turning back to a colder
number. Wait approximately 3 minutes. Listen for compressor to start.
Unit turned off and then on too quickly. Turn unit off and wait 3 minutes before restarting.
Thermostat set too low. Adjust thermostat to higher number for cooling.
O
O
Air conditioner
cooling, but room
is too warm- ice
forming on cooling
coil behind
decorative front.
Outdoor temperature below 64 F(18 C). To defrost the coil, set selector to FAN position.
Then, set thermostat to warmer position.
Air conditioner
cooling, but room
is too warm- NO
ice forming on
cooling coil behind
decorative front.
Thermostat set too warm. Turn thermostat clockwise to a colder setting.
Air directional louvers positioned improperly. Position louvers for better air distribution.
Front of units is blocked by drapes, blinds, furniture, etc. - restricts air distribution. Clear blockage .
Doors, windows, registers, etc. Open- cold air escapes. Close doors, windows, registers.
Air conditioner
turns on and off
rapidly
Noise when
unit is
cooling
Water dripping
INSIDE when
unit is cooling.
Improper installation. Tilt air conditioner slightly to the outside to allow water drainage. Refer to installation
instructions - check with installer.
Dirty air filter- air restricted. Clean air filter.
Air movement sound. This is normal . If too loud, turn selector to lower FAN setting.
Outside temperature extremely hot. Set to ,High, Cool to bring air past cooling coils more frequently.
Sound of fan hitting water-moisture removal system. This is normal when humidity is high.
Close doors, windows and registers.
Window vibration - poor installation. Refer to installation instructions or check with installer.
Water dripping
OUTSIDE when
unit is cooling.
Unit removing large quantity of moisture from humid room. This is normal during excessively humid days
Note: A highly recommended troubleshoot for any issue in general consists of
turning off unit and unplugging for 5 minutes. It is also recommended to try
another outlet. .
O
O
O
O
O
O
O
O
O
O