Page 20

MICROTEL
DialStat
TM
16
NOTE:
If C=5, the Power Fault channel, the response is:
Example Command:
**531
Response:
Power fault channel is READY
Command: **530
Response:
Power fault channel is OFF
NOTE:
When channel 5 is configured OFF it will not call out when a power
failure occurs
Telephone Numbers
As described in the theory of operation in Chapter 1, DialStat
TM
can store up to eight (8)
phone numbers in the System Telephone Directory. This section explains how to
program the dialer’s telephone numbers and shows how to customize the numbers for
certain call-out situations.
Use the following command to enter each telephone number into DialStat
TM
:
*6n
Review Telephone n (n=1 to 8)
**6np**
Program Telephone n (n=1 to 8)
p = telephone number of up to 30 digits with escape codes for one of 8 (eight) telephone
numbers. The telephone data is terminated with ‘**’ (two asterisks).
Example- Command:
**612760571**
Response: Telephone number one is two seven six zero five seven one
Example- Command:
**652432400**
Response:
Telephone number five is two four three two four zero zero
These phone numbers may be customized to use the Call Progress features of the dialer.
Refer to the Advanced Topics chapter for a full discussion about using these powerful
features of the DialStat
TM
Dialer.
Operations
This section details operation of the dialer, from both local and remote locations.
Sections will detail the following actions:
z Alarm Acknowledgment
z System Status