Troubleshooting, Page 26 laars heating systems – LAARS M4-Ext - Installation Manual User Manual
Page 26

Page 26
LAARS Heating Systems
TROUBLESHOOTING
TEMPERATURE INPUTS
Display shows Sensor OPEN
Check the sensor is connected and the wires are continuous to the M4. Finally follow the
procedure for Incorrect Temperature Display.
Display shows Sensor SHORT
The M4 sees a short across the input terminals. Remove the wires from either the SYSTEM
TEMP or OUT TEMP terminals (whichever is reading SHORT). The display should change to
read OPEN. If it doesn’t, the M4 may be damaged.
Display shows an Incorrect Temperature Display
Remove the wires from either the SYSTEM TEMP or OUT TEMP terminals (whichever is
reading incorrectly). The display should change to read OPEN. If it doesn’t, the M4 may be
damaged. Take an ohm reading across the detached sensor wires. The ohm reading should
correspond to the side chart. If it doesn’t, the sensor may be damaged.
CONTROL OPERATION
No Heat
•
(Check Diagram on next page)
Too Much Heat
Check if the control has any of the following:
•
Domestic Hot Water call - The M4 will raise the temperature of the system to either 200˚F or
Maximum Water Temperature on a DHW call, connected to terminals 29 and 30. Check to see
if there is a call for DHW and the length of time it lasts.
•
Reset Ratio and Offset - If excessive heat occurs only in certain weather, adjust the Reset
Ratio and Offset (See Understanding Operating Concept). If excessive heat occurs year round,
reduce the Offset.
•
Boiler Mode Settings - The M4 will only modulate boilers their mode is set to Auto or
Standby. Check to if any boiler stage is set to Manual or On.
•
Control
Settings
- The Last Stage Hold will allow only the Lead boiler to stay on for an
additional number of degrees. If the setting is too high, and only the Lead boiler is on, the
system can over heat. Reduce the Last Stage Hold setting.
Too Little Heat
Check if the control has any of the following:
•
Reset Ratio and Offset - If reduced heat occurs only in certain weather, adjust the Reset
Ratio and Offset (See Understanding Operating Concept). If reduced heat occurs year round,
increase the Offset.
•
Setback and Day/Night Schedule - If reduced heat occurs only during specific hours, check
the Day/Night Schedule and the Setback values. Either reduce the Setback setting or change
the Day and Night Schedules.
•
Boiler Mode Settings - The M4 will only modulate boilers their mode is set to Auto or Standby. Check to if any boiler stage is
set to Manual, Off, or Standby.
Boilers are Short-Cycling
•
Lag
Delay
- Increase the Lag Delay only if all boilers tend to short-cycle.
•
Last Stage Hold - Increase the Last Stage Hold only if the lead boiler tends to short-cycle.
System is Overshooting or Undershooting
•
Gain
- If the system is overshooting reduce the Gain.
•
Gain
- If the system is undershooting increase the Gain.
Temperature Sensor Chart
TEMPERATURE
(in Degrees °F)
Value
(in Ohms)
-30
117720
-20
82823
-10
59076
0
42683
10
31215
20
23089
25
19939
30
17264
35
14985
40
13040
45
11374
50
9944
55
8714
60
7653
70
5941
80
4649
90
3667
100
2914
110
2332
120
1879
130
1524
140
1243
150
1021
160
842
170
699
180
583
190
489
200
412
210
349
220
297
230
253
240
217
250
187