LAARS Modulating Controls M4 & M4-EXT
DAY/NIGHT SCHEDULES
(Available when "Day/Night Schedules" is selected from the Setback Startup
menu option only)
Button: MENU/
The M4 has two levels of heat. The Day level is used when a building is occupied and
people are active.
•
The Night (Setback) level is used when a building is not occupied, or when people are
sleeping. This setting reduces the calculated temperature by the Setback setting. If
the Day calculated water temperature was 150˚F and the Setback was 20˚F, the Night
Schedule will run at (150˚F - 20˚F) = 130˚F.
BACK
SELECT
--- DAY/NIGHT SCHEDULES ---
Set Time
**:**
Day Schedule
**:**
Night Schedule
**:**
•
If the Boost feature is being used, it uses the Day Schedule as a Boost ending point. That is, if the Day Schedule is set to start
at 6:00AM, the Boost will start 30 minutes prior to the Day setting at 5:30AM. The M4 will then raise the calculated water
temperature by the Setback amount. Using the previous example, at 5:30AM the M4 will raise the calculated water to 170˚F
(150˚F + 20˚F) until 6:00AM.
SET TIME
Button: MENU/
Button: MENU/
Adjust the time by selecting Time from the menu and then scrolling through the hours
followed by the minutes. If hours are to be set to PM, scroll through the AM hours to
reach the PM hours.
BACK
SAVE
----- SET PRESENT TIME -----
11:**Pm
CAUTION
Remember that the battery is the backup for the Time. If no power is supplied to the M4 and there
was no battery or battery had no power, time values will be lost and will need to be reset.
HISTORY
Button: MENU/
the previous 24 hours. The temperatures are sampled every 12 minutes. That is, readings of
both System and Outdoor temperatures are recorded and stored every 12 minutes for the last
24 hours.
•
To view the values of specific time period, use the two middle buttons to scroll to that
time and read the upper left temperature.
•
The first screen will be the System Temperature History. By clicking on the Next button,
you'll be able to view the Outdoor Temperature History.
BACK
NEXT
--- SYS= 91 F, 10:57Am ---
BACK
EXIT
--- OD= 54 F, 11:36Am ---