beautypg.com

LAARS Rheos+ RHHV - Install and Operating Manual User Manual

Page 38

background image

Rheos+ Boiler and Water Heater

Page 37

Figure 25 - Gas/Air Test Panel

Figure 26 - Test Panel Valves

5. Remove the two plugs from the + and – ports of

the air orifice taps, thread hose barbs into the

1/8" NPT connections, and attach the manometer

pressure lines to the barbs. Be sure all

connections are gas tight.

6. Switch on the appliance power switch located on

the front of the unit.

7. The Rheos+ will enter the start sequence. The

blower and pump come on for pre-purge, then

the ignitor warm-up sequence starts and after all

safety devices are verified, the gas valve opens. If

ignition doesn’t occur, check that there is proper

gas supply. Wait 5 minutes and start the unit

again.

8. Open air orifice test port valves. Check air

orifice differential at full fire, and make note of

the differential.

9. Switch the Rheos+ off.

10. Close air orifice valves, remove the barbs and

replace the plugs. Make sure the connections are

gas tight.

11. Remove the two plugs from the + and – ports of

the gas orifice taps, thread hose barbs into the

1/8" NPT connections, and attach the manometer

pressure lines to the barbs. Be sure all

connections are gas tight.

12. Switch on the appliance power switch located on

the front of the unit.

13. The Rheos+ will enter the start sequence. The

blower and pump come on for pre-purge, then

the ignitor warm-up sequence starts and after all

safety devices are verified, the gas valve opens.

14. Open gas orifice test port valves. Check gas

orifice differential at full fire, and make note of

the differential.

15. Close gas orifice valves, remove the barbs and

replace the plugs. Make sure the connections are

gas tight.

16. If gas and air orifice differentials match what is

shown in Table 7, and do not differ from each

other by more than 0.1" w.c., the unit is properly

set up. If not, consult, the factory.

17. After placing the appliance in operation, the

Burner Safety Shutoff Device must be tested.

To test:

(a) Close gas shutoff valve with burner

operating.

(b) The flame will go out and blower will

continue to run for the post purge cycle.

One additional attempt to light will follow

including pre-purge, ignitor on, valve/flame

on and post purge. Ignition will not occur

as the gas is off. The ignition control will

lockout, and will have to be reset before the

unit will operate.

Valve

Shown

Closed

Valve

Shown

Open

This manual is related to the following products: