Laars Heating Systems Company is changing the published Service Clearances for Rheos and Rheos+
products. The Service Clearances will now be as follows:
APPLIANCE
SERVICE
ACCESS
SURFACE
CLEARANCE
Piping Side
24" 61cm
Opposite Side
24" 61cm
Top
24" 61cm
Back
36" 91cm
Front
36" 91cm
Vent
Per UL1738
The Rheos and Rheos+ Clearances to Combustibles will remain the same:
APPLIANCE CLEARANCE
FROM
SURFACE
COMBUSTIBLE
MATERIAL
Piping Side
1"
2.5 cm
Opposite Side
1"
2.5 cm
Top
1"
2.5 cm
Back
1"
2.5 cm
Front
1"
2.5 cm
Vent
Per UL1738
All Rheos and Rheos+ literature will be revised to reflect these changes.