LAARS Heating Systems

Page 28

another 20-25°F (11-14°C) (when at high fire), and

it leaves the boiler at 160-165°F (71-74°C). This hot

water is then sent to the system.

If the water at the inlet of the copper heat

exchanger is 140°F (60°C), or higher, the water will be

allowed to flow through the copper heat exchanger and

directly to the outlet of the Rheos+, and there will be a

20-25°F (11-14°C) temperature rise between the inlet

and outlet of the unit, when the unit is at high fire.

The by-pass mixing control displays the mixed

water temperature, which is the temperature of the

water that is sent to the copper heat exchanger. This

temperature setting is locked and cannot be changed in

the field.

By pressing and holding the two buttons on the

left of the mixing control for at least 3 seconds, the

user will access two available menus.

The first menu allows selection of the temperature

units. Pressing the two left buttons for at least 3 seconds

displays “Uni” on the screen (for units). Then “°F” is

displayed. Press the up or down arrow on the control to

change from °F to °C, or °C to °F. When the preferred

selection is displayed, press the enter (bottom left) button.

The control will then display “Add” for the second

menu. If no more buttons are pushed, the control will

automatically return to the temperature display mode.

changed. This setting will be the best suited to most

Rheos+ installations.

Fast: Switch 4 to ON position and all others

to OFF. If the rate of system recovery to setpoint is

sluggish with the control set to medium, the “Fast”

setting may be an improvement. The “Fast” setting

will only be used when the rate of change at the sensor

is very rapid. In most cases, this setting is too fast for

the Rheos+.

5.6 Mixing System and Control

The Rheos+ has an internal mixing system

that ensures that the condensation does not occur

on the finned copper heat exchanger, with boiler

return temperature down to 70°F (21°C). This

system, that consists of automatically actuated

and linked valves, is set up at the factory, and is

non-adjustable. The return water goes through the

stainless steel heat exchanger, then to the mixing

system (see Figure 7).

If the water at the inlet of the copper heat

exchanger is less than 140°F (60°C), water from the

outlet of the copper heat exchanger will be directed

back to the inlet of the copper heat exchanger, and will

mix to bring the inlet water up to 140°F (60°C). Once

through the copper heat exchanger, the water picks up

Control Parameters:

Setpoint = 120°F / 49°C

Differential = 15°F / 8°C

Offset = 15°F / 8°C

Throttling Range = 5°F / 3°F

Minimum Output = 25% (Factory Setting)

100°F

38°C

41°C

105°F

43°C

110°F

46°C

115°F

49°C

120°F

100%

75%

50%

0%

25%

Throttling

Differential

Offset

Note: As shown, if the offset is set the same as the differential, the throttling range is outside the differential range.

The only time the Rheos+ will be above 25% fire is when the temperature drops below the setpoint's differential.

Line with arrows represents what happens after the Rheos+ achieves 120°F/49°C during a call for heat. It will cool to

105°F/41°C, and will re-energize at 25% of full fire.1°C.

Rheos+ Inlet Temperature

%

of

Full

Fire

Range

Figure 16 - Control Parameter Possible Interference