2 model identification, 3 warranty, 4 dimensions – LAARS Mighty Therm2 MT2V (Sizes 200, 300, 400) - Install and Operating Manual User Manual
Page 4: 5 locating the appliance
LAARS Heating Systems
Page 4
1.2 Model Identification
Consult the rating plate on the unit. The
following information describes the model number
structure.
Model Character Designation
1-3 Model Series Designation
M T 2 = Mighty Therm2
4 Usage
H = Hydronic
V = Volume Water
5-8 Size
0 2 0 0 = 199,900 BTU/h input
0 3 0 0 = 300,000 BTU/h input
0 4 0 0 = 399,900 BTU/h input
9 Fuel
N = Natural Gas
P = Propane
10 Altitude
A = 0-10,000 feet
11 Location
C = Indoor and Outdoor
12 Firing Mode
C = On-Off (standard)
K = Two-stage (optional)
13 Revision
2 = Revision Level 2
14 Heat Exchanger
B = Glass-lined CI / copper / brz trim (std. MT2V)
C = Glass-lined cast iron / copper (std. MT2H)
N = Glass-lined cast iron / cu-nickel
P = Glass-lined cast iron / cu-nickel / brz trim
2 = Glass-lined cast iron / copper, brz trim, HLW
5 = Glass-lined cast iron / cu-nickel / brz, HLW
15 Options Code
X = Standard unit
L = Low temperature control (std. MT2V)
16 Pump Options
X = No Pump
N = Pump mounted, normal water, Taco
S = Pump mounted, soft water pump (MT2V
only), Taco
G = Pump mounted, normal water, Grundfos
1.3 Warranty
Laars Heating Systems’ Mighty Therm2
appliances are covered by a limited warranty. The
owner should fill out the warranty registration card and
return it to Laars Heating Systems.
All warranty claims must be made to an
authorized Laars Heating Systems representative or
directly to the factory. Claims must include the serial
number and model (this information can be found
on the rating plate), installation date, and name of
the installer. Shipping costs are not included in the
warranty coverage.
Some accessory items are shipped in separate
packages. Verify receipt of all packages listed on
the packing slip. Inspect everything for damage
immediately upon delivery, and advise the carrier of
any shortages or damage. Any such claims should be
filed with the carrier. The carrier, not the shipper, is
responsible for shortages and damage to the shipment
whether visible or concealed.
1.4 Dimensions
See Figures 1A and 1B.
1.5 Locating the Appliance
The appliance should be located to provide
clearances on all sides for maintenance and inspection.
It should not be located in an area where leakage of
any connections will result in damage to the area
adjacent to the appliance or to lower floors of the
structure.
When such a location is not available, it is
recommended that a suitable drain pan, adequately
drained, be installed under the appliance.
The appliance is design certified by CSA-
International for installation on combustible flooring;
in basements; in closets, utility rooms or alcoves.
Mighty Therm2 Boilers or Water Heaters must
never be installed on carpeting. The location for the
appliance should be chosen with regard to the vent
pipe lengths and external plumbing. The unit shall be
installed such that the gas ignition system components
are protected from water (dripping, spraying, rain, etc.)
during operation and service (circulator replacement,
1 2 3
4 5 6 7 8 9
10
11
12
13
14
15
16
M T 2
A
C
2
SERIES
M T 2
USAGE
H
V
SIZE
0 2 0 0
0 3 0 0
0 4 0 0
FUEL
N
P
ALTITUDE
A
FIRING
MODE
C
K
LOCATION
C
REVISION
2
HEAT
EXCHANGER
B
C
N
P
2
5
OPTIONS
CODE
X
L
PUMP
OPTIONS
X
N
S
G