LAARS MagnaTherm MGV - Installation, Operation and Maintenance Instructions User Manual
Page 74

LAARS Heating Systems
Page 70
Code
Description
Lockout
or Hold
Procedure
11
Internal fault:
Invalid burner control state flag
L
Internal fault
1. Reset module
2. If fault repeats, replace module.
12
Internal fault:
Safety relay drive cap short
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
13
Internal fault:
PII (Pre-Ignition Interlock) shorted to
ILK (Interlock)
H or L
Internal fault
1. Reset module
2. If fault repeats, replace module.
15
Internal fault:
Safety relay test failed due to feedback
ON
L
Internal fault
1. Reset module
2. If fault repeats, replace module.
16
Internal fault:
Safety relay test failed due to safety
relay OFF
L
Internal fault
1. Reset module
2. If fault repeats, replace module.
17
Internal fault:
Safety relay test failed due to safety
relay not OFF
L
Internal fault
1. Reset module
2. If fault repeats, replace module.
18
Internal fault:
Safety relay test failed due to feedback
not ON
L
Internal fault
1. Reset module
2. If fault repeats, replace module.
19
Internal fault:
Safety RAM write
L
Internal fault
1. Reset module
2. If fault repeats, replace module.
20
Internal fault:
Internal fault: Flame ripple and overflow
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
21
Internal fault:
Flame number of sample mismatch
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
22
Internal fault:
Flame bias out of range
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
23
Internal fault:
Bias changed since heating cycle starts
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
24
Internal fault:
Spark voltage stuck low or high
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
25
Internal fault:
Spark voltage changed too much during
flame sensing time
H
Internal fault
1. Reset module
2. If fault repeats, replace module.