3 model identification, 4 warranty, Model nomenclature – LAARS MagnaTherm MGV - Installation, Operation and Maintenance Instructions User Manual
Page 6: Laars heating systems
LAARS Heating Systems
Page 2
Model Nomenclature
1 2
3
4 5 6 7 8
9
10
11
12
13
M G
1
SERIES
M G
USAGE
H -
HYDRONIC
V -
VOLUME
WATER
SIZE
MBTU/h
2 0 0 0
2 5 0 0
3 0 0 0
3 5 0 0
4 0 0 0
FUEL
N -
NATURAL
P -
PROPANE
COUNTRY
CODE
X -
USA/
CANADA
E -
EXPORT
*
OPTIONS CODE
X -
STANDARD
J
- CSD-1
ELEC SYSTEM
A - 110V, 1Ø
B - 220V, 1Ø
C - 208V, 3Ø
D - 480V, 3Ø
E - 600V, 3Ø
REVISION
1 -FIRST
ASME
X -
“H” STAMP (MGH)
W -
“HLW” STAMP (MGV)
1.4 Warranty
LAARS Heating Systems MagnaTherm boilers are
covered by a limited warranty. The owner should
complete the warranty registration at
http://www.LAARS.com
ALL WARRANTY CLAIMS must be made by an
authorized LAARS Heating Systems representative.
Claims must include the serial number and model
(this information can be found on the rating plate).
All claims must also include the installation date and
name of the installer. Shipping costs are not included
in the warranty coverage.
1.3
Model Identification
Consult the rating plate on the unit. The following
information describes the model number structure.
(1-2) Model Series Designation
M G = MagnaTherm
(3) Usage
H = Hydronic
V = Volume Water
(4-7) Size
2 0 0 0 = 1,999,000 BTU/hr input
2 5 0 0 = 2,499,000 BTU/hr input
3 0 0 0 = 3,000,000 BTU/hr input
3 5 0 0 = 3,500,000 BTU/hr input
4 0 0 0 = 4,000,000 BTU/hr input
(8) Fuel
N = Natural Gas
P = LP Gas
(9) Country Code
X = USA / CANADA
E - Export (CE - non CSA)
(10) Option Code
X = Standard Unit
J = CSD1 Version
(11) Electrical System
A - 110V, (Single Phase)
B - 220V, (Single Phase)
C - 208V, (Three Phase)
D - 480V, (Three Phase)
E - 600V, (Three Phase)
(12) Additional Options
X - “H” STAMP (MGH)
W - “HLW” STAMP (MGV)
(13) Revision
1 = First
*
Not CSA approved
Altitude:
Gas input rating of the MagnaTherm shall be used for
elevations up to 2000 ft (600 m). The input rating at
elevations above 2000 ft (600 m) shall be reduced at
a rate of 4 percent for each 1000 ft (300 m) above sea
level before selecting the equipment size.
WARNING
Electrical Shock Hazard
Electrical shock can cause severe injury, death or
property damage. Disconnect the power supply
before beginning installation or changing the
wiring to prevent electrical shock or damage to the
equipment. It may be necessary to turn off more than
one power supply disconnect.
All electrical wiring is to be done in accordance with
local codes, or in the absence of local codes, with:
1) The National Electrical Code ANSI/NFPA No.
70 - latest Edition, or 2) CSA STD. C22.1 “Canadian
Electrical Code - Part 1.” This appliance must be
electrically grounded in accordance with these codes.
WARNING
MagnaTherm units must be installed in
accordance with the procedures detailed in this
manual, or the LAARS Heating Systems warranty
will be voided. The installation must conform to
the requirements of the local jurisdiction having
authority, and, in the United States, to the latest
edition of the National Fuel Gas Code, ANSI
Z223.1/NFPA54. In Canada, the installation
must conform to the latest edition of CSA
B149.1 Natural Gas and Propane Gas Installation
Code, and/or local codes. Where required by the
authority having jurisdiction, the installation
of MagnaTherm boilers must conform to the
Standard for Controls and Safety Devices for
Automatically Fired Boilers, ANSI/ASME CSD-1.
Any modifications to the boiler, its gas controls, or
wiring may void the warranty. If field conditions
require modifications, consult the factory
representative before initiating such modifications.