IGE - 9. Removal of the Gas Valve Assembly:

CAUTION

120 volt potential exposure. Isolate the appliance

and reconfirm power has been disconnected

using a multimeter.

a.

Remove the burner manifold, refer to

section 8-a,b,c.

b.

Remove the four (4) Phillips screws that

hold the gas connection and gas control

valve in place at the bottom of the unit.

Pull the gas connection down to

disconnect it from the gas valve assembly.

Inspect o-ring for damage and/or defects.

Ensure o-ring is in place when

re-assembling this connection.

c.

Disconnect connectors from solenoids,

note which connector goes to each

solenoid, along with the proper wire

colors. Pull gas valve assembly out of unit.

IGE - 10. Removal of Heat Exchanger:

CAUTION

120 volt potential exposure. Isolate the appliance

and reconfirm power has been disconnected

using a multimeter.

a.

Remove PCB unit, refer to section 2-a.

b.

Remove the heat exchanger water

connection lines, refer to section 3-a.

c.

Remove the three (3) Phillip screws

securing the gas manifold assembly to the

gas control valve.

d.

Remove the six (6) Phillip screws that

secure the heat exchanger assembly in

place.

e.

Disconnect connectors B1, B5, B6, C1, C3,

F1and F8. These are the igniter, flame rod,

thermo-fuse, hot water inlet and outlet

thermistor, and the anti-freeze heater

connections.

f.

Pull the heat exchanger out of the heater.

g.

Transfer all components found on the old

heat exchanger over to the new exchanger.

50