Connecting the cable, Testing the reader, Removing the cover – Interlogix T-500 User Manual
Page 2

Figure 4. Aligning base plate and top cover
8. Verify the connection is secure and install the
security screws on the top and bottom of the
reader.
9. Cover the exposed screws with the rubber
plugs provided.
Figure 5. Gasket detail
Connecting the Cable
1. The readers are supplied with a 12-conductor
cable pigtail with drain wire. Connect the pigtail
to the host panel. Use the Cable Connection
Chart (below) to correctly match the color of
each wire.
Color
Signal
Red
6 to 16 VDC
Black
Ground
Green
Data 0
White
Data 1
Orange
Green LED Control
Brown
Red LED Control
Yellow
Beeper Control
Gray
Door DI
Pink
REX DI
Tan
Tamper Output
Blue
Hold
Purple
Reserved
........
Drain Wire
2. Use a DC Power source between 6-16 VDC.
3. Verify the reader is properly grounded by
attaching the ground wire to an earth ground
connection at the power supply or field panel
end of the cable. Connect reader’s drain wire
to the cable shield. Connect shield wires at the
field panel. The recommended cable gauge is
18-gauge to 22-gauge. Check with the cable
supplier to determine the best choice for the
application and installation distance.
Testing the Reader
1. Power up the reader. Verify the power-on self
test
LED/beep sequence:
- green LED flashes; two short beeps
- yellow LED flashes; three short beeps
- red LED flashes.
- yellow LED flashes.
2. Verify the yellow LED is on continously
indicating the reader is ready.
3. Present a badge that has been properly
enrolled in the system. Verify the yellow LED
flashes and a short beep is heard.
Removing the Cover
1. Remove all security screws.
2. Pull cover off the base. Refer to Figure 4 on
Base plate
Top cover