beautypg.com

Step 9 — install all accessories, In. diameter and, Fig. 24 — typical economi$er sensor wiring – Carrier 50TJ016-028 User Manual

Page 15

background image

15

VENTILATION AIR (Minimum Position Set Up) — If ven-
tilation air is not required, skip this section. If ventilation air is
required, perform the following:

1. The indoor fan must be on to set the ventilation air.

Either put the thermostat in the continuous fan mode or
jumper the R and G terminals at the rooftop unit con-
nection board.

2. Locate the minimum position (MIN POS) potentiometer.

Turn the potentiometer full CCW to fully close the out-
door air dampers. Turn the potentiometer gradually
clockwise (CW) to the desired position. See Fig. 16.

3. Replace the filter access panel. See Fig. 18. Ensure the fil-

ter access panel is securely engaged.

4. Calculate the minimum airflow across the EconoMi$er.

a.

Calculate % of outside air using the following
formula.
% Outdoor air through EconoMi$er

b. Multiply total CFM by percentage outdoor air, this

gives outdoor air volume in CFM.

Step 9 — Install All Accessories —

After all the

factory-installed options have been adjusted, install all field-
installed accessories. Refer to the accessory installation instruc-
tions included with each accessory.
MOTORMASTER® I CONTROL INSTALLATION
(50TJ016 and 020 Only)
Install Field-Fabricated Wind Baffles — Wind baffles must
be field-fabricated for all units to ensure proper cooling cycle
operation at low ambient temperatures. See Fig. 25 for baffle
details. Use 20-gage, galvanized sheet metal, or similar
corrosion-resistant metal for baffles. Use field-supplied screws
to attach baffles to unit. Screws should be

1

/

4

-in. diameter and

5

/

8

-in. long. Drill required screw holes for mounting baffles.

% Outdoor air =

Mixture Temp – Return Air Temp
Outdoor Temp – Return Air Temp

Personal Injury Hazard. Avoid possible injury by keep-
ing fingers away from damper blades.

To avoid damage to the refrigerant coils and electrical com-
ponents, use recommended screw sizes only. Use care
when drilling holes.

20 mA LED

1k ohm Potentiometer

2 to 10 VDC at

0 to 2000 ppm

CO2 Sensors:

Rem ote

M inim um Position

Rem ote

LED

Outdoor Air Enthalpy

CROUTENT001A00

Return Air Enthalpy

CRRETENT001A00

Line

Voltage

CO
CO
COM
DAT
COM
REM
POT
COM
LED
COM

2
2

OAT
COM
OAH
+15V
RAT
COM
RAH
+15V

C

O

M PW

O

U

T T

T

Violet

C

O

M PW

O

U

T T

T

Violet

Field-supplied W iring

W iring Included

470 ohm

5 watt

Resistor

24 VAC m ust be present

on BI for the system to be

unoccupied.

Unoccupied Control

(Part num ber on the control

m ust be AD-DM E1701-1

or AD-DM E1711-1.)

Unoccupied

Contact

Tan
Violet
W hite
Red

Tan
Violet
W hite
Red

24 V

A

C

20 V

A

NOT

USED

1

2

-

(+)

3

2

3ZCSENCO

Fig. 24 — Typical EconoMi$er Sensor Wiring