Table 7.6: summary of vertical venting options – Crown Boiler MWC116ENL User Manual
Page 19
17
Permitted Terminals for Vertical Venting
6)
- Use Crown PN 230532
with the appropriate flashing (Table 7.3b)
Vertical Vent Terminal Locations (Vent Option 5)
7)
- Observe the following limitations on the location of all
vertical vent terminals (see Figure 7.7):
The top of the vent pipe must be at least 2 feet above any object located within 10 feet.
•
The bottom of the air inlet terminal must be at least 12” above the normal snow accumulation that can be
•
expected on the roof. The terminal used in Vent Option #5 has a fixed distance above the storm collar of
19”. If a greater distance is needed to provide the clearance above the snow line, build a chase on the
roof and mount the vertical terminal on top of the chase.
Wall thimbles
8)
– Concentric vent has a “zero” clearance to combustibles and therefore does not require the
use of wall thimbles.
Pitch of Horizontal Piping
9)
- Pitch all horizontal piping so that any condensate which forms in the piping will run
towards the boiler. Pitch Crown horizontal concentric venting 5/8” per foot
Supporting Pipe
10)
- Vertical and horizontal sections of pipe must be properly supported. Support Crown
concentric venting near the female end of each straight section of pipe. Exception: Vertical runs of concentric
pipe in an unused chimney (Figure 7.36) need only be supported at the terminal and at the base of the run.
table 7.5: Vent/ air Intake Fitting Equivalent length
VENT FITTING
EQUIVALENT LENGTH (ft)
60/100mm 90° CONCENTRIC ELBOW
4.5
60/100mm 45° CONCENTRIC ELBOW
4.0
80/125mm 90° CONCENTRIC ELBOW
8.5
80/125mm 90° SWEEP CONCENTRIC ELBOW
5.5
80/125mm 45° CONCENTRIC ELBOW
3.0
80/125mm 90° CONCENTRIC SUPPORT ELBOW
8.5
table 7.6: Summary of Vertical Venting options
VENT OPTION #
5
6
CLASSIFICATION USED IN THIS
MANUAL
VERTICAL
CONCENTRIC
RESERVED FOR
FUTURE USE
ILLUSTRATED IN FIGURE
7.7
VENT PIPE PENETRATION
THROUGH STRUCTURE
ROOF
VENT PIPE SIZE
80/125mm
CONCENTRIC
INLET AIR ORIFICE SIZE
82mm
MAX. VENT LENGTH
27ft - 10in
MIN. VENT LENGTH
6in
VENT TERMINAL
CROWN #230532
CONCENTRIC
TERMINAL (TABLE
7.3b)
VENT MATERIAL
CROWN 80/125 mm
VENT COMPONENTS
SHOWN IN TABLE
7.3b