beautypg.com

Installation instructions (cont’d), Venting (cont’d) gas piping, Awarning – Kenmore POWER MISER 153.336851 User Manual

Page 14

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Installation Instructions (cont’d)

Venting (cont’d)

Gas Piping

All vent gases must be completely vented to the outdoors of the

structure (dwelling). Install only the draft hood provided with
the new water heater and no other draft hood.

Vent pipes must be secured at each joint with sheet metal screws.

MIN. % INCH

PER LINEAR

FOOT

TO

CHIMNEY

VENT PIPE INSTALLATION

There must be a minimum of 6" clearance between single wall

vent pipe and any combustible material. Fill and seal any clear-

single wall vent pipe and combustible material

with mortar mix, cement, or other noncombustible substance.

For other than single wall, follow vent pipe manufacturers clear­

ance specifications. To insure a tight fit of the vent pipe in a
brick chimney, seal around the vent pipe with mortar mix
cement.

AWARNING

Mate sure the gas supplied is the same type listed on the
mc^d rating plate. The inlet gas pressure must not exceed

10.5 in. water coiumn (2.6kPa) ior natural gas or 13 in. water

column (3.2kPa) for propane (LP.) gas. The minimum miet

gas pressure listed on the model rating plate b for the pur^

pose of input adjustment

AWARNING

If the gas control valve b subjected to pressures exceeding

'A

pound per square inch (3.5kPa), the damage to the gas con­

trol valve could result in a fire or explosion from leaking gat

AWARNING

If the main gas line shutoff serving all gas appliances b used,
also turn “OFF" tte gas at each appliance. Leave all gas appli­
ances shut off until the water heater installation b complete.

AWARNING

Failure to have required clearances between vent piping and
combustible material will result in a fire hazarxl.

AWARNING

Be sure vent pipe b properly connected to prevent escape of
dangerous flue gases which could cause deadly asphyxiation.

AWARNING

Chemical vapor corrosion of the flue and vent system may
occur if air for combustion contains certain chemical vapors.
Spray can propellants, cleaning solvents, refrigerator and air
conditioner

r^^rants,

swimming

pool chemicals, calcium

and sodium chloride,

waxes,

bleach, and process chemicals are

typical compounds which are potentially corrosive.

A gas line of sufficient size must be run to the water heater.

Consult the latest edition of National Fuel Gas Code ANSI
Z223.1, also referred to as NFPA54 and the gas company concern­
ing pipe size.

There must be:

• A n^ly accessible manual shut off valve in the gas supply line

serving the water heater, and

• A drip W (sediment trap) ahead of the gas control valve to help

prevent mtt and foreign materials from entering the gas control

valve.

• A flexible gas connector or a ground joint union between the

shutoff valve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting the

water heater. Use a soapy water solution, not a match or open

flame. Rinse off soapy solution and wipe dry.

Standard Modeb are for installation up to 3,300 feet above sea
level.

High Altitude Modeb are for installation from 3,300 to 5,500
feet above sea level.

If a standard model is installed above 3,300 feet or a high altitude
model is installed above 5,500 feet, the input rating must be
reduced at the tate of 4 percent for each 1,000 feet above sea level.
Contact your local Scars Service Center or gas utility for further
information.

14