5wire wallplate or subbase – Honeywell Y8185 User Manual
Page 3
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
Fig. 3—Leveling methods for wallplate or subbase.
5
WIRE WALLPLATE OR SUBBASE
Follow the Instructions provided by the heating or
heating/coollng equipment manufacturer. If not avail-
able, refer to TYPICAL WIRING DIAGRAMS at end of
this publication,
NOTE: Aii wiring must comply with local electrical
codes and ordinances.
FOR WALLPLATE (Heating-Only System)
□
Refer to Fig. 4 and strip thermostat wire insulation
as necessary.
Q Connect wires to R, W, and C terminals. Firmly
tighten screws. The timer is powered by the system’s
low voltage transformer. NOTE: An unmarked fourth
terminal is provided for 3-wire [series 20} primary
controls (Fig, 11).
n Push excess wire back into wall.
□
Plug hole in wall with nonhardening caulk, putty,
or nonflammable insulation to prevent drafts from affect
ing thermostat operation.
FOR SUBBASE (Heating/Cooling Systems)
ED Refer to Fig. 4 and strip thermostat wire insulation
as necessary.
□ Connect the wires to corresponding terminals on
the subbase.
If labels do not agree with your new subbase—
—Refer to Table 2 or Figs. 12-15.
—Determine correct hookup from the listed control
function and the equipment control circuit.
The timer is powered by the system's low voltage
transformer. 24 Vac must be maintained across termi
nals R and C.
TABLE 2—TERMINAL DESIGNATIONS
SUBBASE
TERMINAL
CONTROL FUNCTION
R
Control transformer power.
W
Heating control circuit.
Y
Cooling control circuit jumper to W
for heat pump compressor control}.
G
Fan control circuit.
C
Timer control (transformer common).
0
Changeover or reversing valve, made
continuously in cool.
B
Changeover or reversing valve made
continuously In heat
□
□
Push excess wire back into wall.
Piug hole in wall with nonhardening caulk, putty,
or nonflammable insulation to prevent drafts from affect
ing thermostat operation.