beautypg.com

Awarning, Awarnin, Adanger – Kenmore THE ECONOMIZER 153.33205 User Manual

Page 14

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

The Discharge Pipe:

• Shali not be smalier in size than the outlet pipe size of the valve, or

have any reducing couplings or other restrictions.

• Shall not be plugged or blocked,
• Shall be of material listed for hot water distribution.
• Shall be installed so as to aflow complete drainage of both the

temperature-pressure relief valve, and the discharge pipe.

• Shall terminate at an adequate drain,
• Shall not have any valve between the relief valve and tank.

ADANGER

Water

temperature

over

125°F

(52°C)

can

cause

severe

burns

instantly resulting In severe injury or

death.

Children,

the

elderly,

and

the

physically or mentally disabled are at

highest risk for scald Injury,

Feel

water

before

bathing

or

showering.

Temperature

limiting

valves

are

available.

Read

instruction

manual

for

safe

temperature setting.

The temperature-pressure relief valve must be manually operated at least
once a year. Caution should be taken to ensure that (1 ) no one is in front
of or around the outlet of the temperature-pressure relief valve discharge
line, and (2) the water manually discharged will not cause any bodily injury
or property damage because the water may be extremely hot.

If after manually operating the valve, it fails to completely reset and

continues to release water, immediately close the cold wafer inlet to
the water heater, follow the draining instructions, and replace the
temperature-pressure relief valve with a new one.

GAS PIPING

AWARNING

Fire and Explosion Hazard

Do not use water heater with any

gas other than the gas shown on

the rating plate.

Excessive pressure to gas control

valve can cause serious injury or

death.

Turn

off

gas

lines

during

installation.

Contact

qualified

installer

or

service agency.

Make sure the gas supplied is the same type listed on the model rating
plate. The inlet gas pressure must not exceed Minch water column (3.5
kPa) for natural and propane gas (L.R). The minimum inlet gas pressure
shown on the rating plate is that which will permit firing at rated input.

Ail gas piping must comply with local codes and ordinances or with the

National Fuel Gas Code (ANSI Z223.1 / NFPA-54) whichever applies. Copper
and brass tubing and fittings (except tin lined copper tubing) shall not be used.

If the gas control valve is subjected to pressures exceeding 1/2 psi

(3.5 kPa), the damage to the gas control valve could result in a fire or
explosion from leaking gas.

If the main gas line Shut-off serving all gas appliances is used, also

turn “off" the gas at each appliance. Leave all gas appliances shut

“off until the water heater installation is complete.

A gas line of sufficient size must be run to the water heater. Consult
the current edition of National Fuel Gas Code ANSI Z223.1/NFPA54and
your gas supplier concerning pipe size.

There must be:

• A readily accessible manual shut off vaive in the gas suppiy line

serving the water heater, and

• A drip leg (sediment trap) ahead of the gas control valve to help

prevent dirt and foreign materials from entering the gas control valve.

• A flexible gas connector or a ground joint union between the shut off

valve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting the water
heater. Use a soapy wafer solution, not a match or open flame. Rinse
off soapy solution and wipe dry.

AWARNIN

I

Breathing Hazard - Carbon Monoxide Gas

High altitude orifice must be installed

for operation above 7,700 ft (2,347 m).

Contact a qualified installer or service

agency

Breathing carbon monoxide can cause brain damage or

death. Always read and understand instruction manual.

Water heaters covered in this manual have been tested and approved
for installation at elevations up to 7,700 feet (2,347 m) above sea level.
When installed at elevations above 7,700 feet (2,347 m), input rating

should be reduced at the rate of 4 percent for each 1,000 feet (305 m)
above sea level which requires replacement of the burner orifice in
accordance with National Fuel Gas Code ANSI Z223.1/NFPA 54. Contact

your local gas supplier for further information.

Failure to replace the standard orifice with a high altitude orifice when
installed at elevations above 7,700 feet (2,347 m) could result in
improper and inefficient operation of the appliance, producing carbon
monoxide gas in excess of safe limits. This could result in serious
injury or death. Contact your gas supplier for any specific changes

which may be required in your area.

AWARNING

Fire and Explosion Hazard

Use

joint

compound

or

compatible with propane.

tape

Leaktestbeforeoperating heater.

Disconnect gas piping and shut-off

valve

before

pressure

testing

system.

Use pipejoint compound or teflon tape marked as being resistant to the
action of petroleum [Propane (L.P.)] gases.

14

This manual is related to the following products: