Constructed houses – Kenmore 5EW1.75 User Manual
Page 9
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
B. All Air from Outdoors: The confined space shall be provided with two permanent openings, one
commencing within 12 inches of the top and commencing within 12 inches of the bottom of the
enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces {crawl or
attic) that freely communicate with the outdoors.
1. When directly communicating with the outdoors, each opening shall have a minimum free area of
one square inch per 4,000 Btu per hour of total input rating of all equipment in the enclosure.
2. When communicating with the outdoors through vertical ducts, each opening shall have a minimum
free>area of one square inch per 4,000 Btu per hour of total input rating of all equipment in the
enclosure.
When communicating with the outdoors through horizontal ducts, each opening shall have a
minimum free area of one square inch per 2,000 Btu per hour of total input rating of all equipment in
the enclosure.
When ducts are used, they shall be of the same cross-sectional area as the free area of the openings to
which they connect. The minimum dimension of rectangular air ducts shall be not less than three
inches.
3.
4.
f=RESH
AIR
DUCT
BOILER
FRESH AIR DUCT CAPACITIES FOR DUCTS SUPPLYING FRESH AIR TO BOILER IN TIGHTLY
CONSTRUCTED HOUSES
Fresh Air
Mesh Screen
Wood Louvers
Metal Louvers
Duct Size
(Btuh)*
(Btuh)*
(Btuh)*
3-'/2”x 12”
144,000
36,000
108,000
8” X 8”
256,000
64,000
192,000
8”x 12”
384,000
96,000
288,000
8”x 16”
512,000
128,000
384,000
*Btuh = British Thermal Units per hour based on opening covered by ‘/4” mesh
screen, wood louvers, or metal louvers.