Start up conditions, Thermal expansion, Thermal expansion tank specifications – Kenmore 153.337002 User Manual
Page 23: Expansion tank sizing chart, Strange sounds, Thermal expansion strange sounds, Troubleshooting guide
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
Start Up Conditions
THERMAL EXPANSION
Water supply systems may, because of high line pressure, fre
quent cut-offs, the effects of water hammer and others, have
installed devices such as pressure reducing valves, check valves,
back flow preventers, etc. to control these types of problems.
When these devices are not equipped with an internal by-pass,
and no other measures are taken, the devices cause the water sys
tem to be closed. As water is heated, it expands (thermal expan
sion) and closed systems do not allow for the expansion of heat
ed water.
The water within the water heater tank expands as it is heated
and increases the pressure of the water system. If the relieving
point of the water heater’s temperature-pressure relief valve is
reached, the valve will relieve the excess pressure. The tempera
ture-pressure relief valve is not intended for the constant
relief of thermal expansion. This is an unacceptable condition
and must be corrected.
It is recommended that any devices installed which could create
a closed system have a by-pass and/or the system have an expan
sion tank to relieve the préSsure built by thermal expansion in
the water system. Expansion tanks arc available for ordering
through the Sears Service Center. Contact the local plumbing
inspector, water supplier, and/or the Sears Service Center for
assistance in controlling these situations.
Thermal Expansion Tank Specifications
Troubleshooting Guide
Model
Tank Capacity
In Gallons
Dimensions in Inches
Pipe Fitting
On Tank
Number
Diameter
Length
153.331050
5
11
inches
14%
inches
Vi'
Male
Expansion Tank Sizing Chart
Expansion
Tank
Capacity
Needed
Inlet*
j
Water
Heat
Water (Gal
er Capacity
ons)
Pressure | 66
73
82
100
40-80psi 5
5
5
5
WATER HEATER
COLD WATER
INLET FITTING
FLOOR, CEIUNG
JOIST, ETC.
‘Highest recorded inlet water pressure in a 24 hour period or
regulated water pressure.
NOTE: Expansion tanks are pre-chatged with a 40 psi air
charge. If the inlet water pressure is higher than 40 psi, the
expansion tank’s air pressure must be adjusted to match that
pressure, but must not be higher than 80 psi.
STRANGE SOUNDS
Possible noises due to expansion and contraction of some metal
C
arts during periods of heat-up and cool-down do not represent
armful or dangerous conditions.
Condensation causes sizzling and popping with the burner area
during heating and cooling periods and should be considered
normal. See “Condensation” section.
23