Sizing instructions – Kenmore 70089 User Manual
Page 5
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
Sizing Instructions
Many complaints about room air conditioners result
from units that are over-sized or under-sized for a given
area. Over-sized units cool an area before humidity can
be adequately removed, so air feels cold and clammy.
Under-sized units do not sufficiently cool an area.
The following table contains guidelines for properly
sizing a room air conditioner for a given area.
To size unit;
1. Determine size (in square feet) of area to be cooled;
locate square footage In far left column of table
below.
2. Choose right-hand column showing location of room
in building:
• Room below attic; insulated ceiling above.
• Room with occupied room above.
■ Top floor under insulated roof.
3. Follow down right-hand column, reading horizontally
from square footage to find approximate air
conditioner capacity (in Btus per hour) required to
adequately cool designated area.
NOTE: When determining size of unit, also consider
conditions at bottom of table. For best results,
choose air conditioner with cooling capacity
(Btus per hour) closest to, but not exceeding,
estimated size.
Required Air Conditioner Cooiing Capacity—Btu/hour
Size of Area
to be Cooled
(in square feet)
Room below
attic; insulated 4^
ceiling above □□
Room with /\
occupied
room above EJ
Top floor under j ■
insulated roof
(no attic)
Li—1
100
3500 to 4000
4000 to 4500
4500 to 5000
150
4000 to 5000
4500 to 5000
5500 to 6500
200
4500 to 5500
5000 to 6000
6000 to 7000
250
5000 to 6000
5500 to 6500
7500 to 8500
300
6000 to 7000
6500 to 7500
8500 to 9500
350
6500 to 7500
7000 to 8000
10000 to 11000
400
7000 to 8000
8000 to 9000
11000 to 12000
450
7500 to 8500
8500 to 9500
11500 to 12500
500
8000 to 9000
9500 to 10500
13000 to 14000
600
9500 to 10500
11000 to 12000
15000 to 16000
700
10500 to 11500
12000 to 13000
17000 to 18000
800
11500 to 13000
13500 to 14500
19000 to 20000
900
12500 to 14000
14500 to 16000
21000 to 22000
1000
13500 to 15000
15500 to 17000
23000 to 24500
1200
16000 to 17500
18000 to 20000
26500 to 28500
1400
18000 to 20000
21000 to 23000
30500 to 32500
1600
20000 to 22000
23000 to 25000
1800
22000 to 24000
25500 to 27500
2000
24000 to 26000
28000 to 30000
Additional conditions:
• If normal occupancy of area is more than two people, add 600 Btu/hour per person. If normal occupancy is one
person, subtract 600 Btu/hour.
• Add 1200 Btu/hour if area includes a kitchen.
• If room is heavily shaded, subtract 10 percent from total capacity. Increase by 10 percent if area is very sunny.