beautypg.com

Temperatyre-pressure relief valve, Installation instructions (cont’d), A warning – Kenmore 153.327366 User Manual

Page 9: Awarning

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Installation Instructions (cont’d)

Temperatyre-Pressure

Relief Valve

A WARNING

At the time of manufacture this water heater was provided
with a combination temperature-pressures relief valve cer­
tified by a nationally recognized testing laboratory that

maintains periodic inspection of production of listed equip­
ment or materials, as meeting the requirements for Relief
Vaives and Automatic Gas Shutoff Devices for Hot Water
Supply Systems, and the current edition of ANSI Z 2 1 . Ï 2
and the code requirements of ASME. If replaced, the valve
must meet the requirements of local codes, but not less
than a combination temperature and pressure relief vaive
certified as meeting the requirements for Relief Valves and
Automatic Gas Shutoff Devices for Hot Water Supply
Systems, ANSI Z2I.22 by a nationally recognized testing
laboratory that maintains periodic inspection of production
of listed equipment or materiais.
The valve must be marked with a maximum set pressure
not to exceed the marked hydrostatic working pressure of
the water heater (ISO lbs. p.s.l.) and a discharge capacity

not less than the water heater input rate as shown on the
model rating plate. (Electric heaters - watts divided by

1000

X

34

i

2 equal BTU/Hr. rate.)

Your local jurisdictional authority, while mandating the use
of a temperature-pressure relief valve complying with
ANSI Z2I.22 and ASHE, may require a valve model differ­
ent from the one furnished with the water heater.

Compliance with such local requirements must be satisfied
by the installer or end user of the water heater with a
locally prescribed temperature-pressure relief valve
installed in the designated opening in the water heater in
place of the factory furnished valve.
For safe operation of the water heater, the relief vaive
must not be removed from It's designated opening or
plugged.

The temperature-pressure relief valve must be installed

directly into the fitting of the water heater designated for

the relief valve. Position the vaive downward and provide

tubing so that any discharge will exit only within 6 inches
above, or at any distance below the structural floor. Be cer­
tain that no contact is made with any live electrical part.
The discharge opening must not be blocked or reduced in
size under any circumstances. Excessive length, over 30
feet, or use of more than four elbows can cause restriction
and reduce the discharge capacity of the valve.

No valve or other obstruction is to be placed between the
relief valve and the tank. Що not connect tubing directly to

discharge drain unless a 6 air gap is provided. To prevent

bodify injury, hazard to life, or property damage, the relief

valve must be allowed to discharge water in quantities
should circumstances demand. If the discharge pipe is not

connected to a drain or other suitable means, the water

flow may cause property damage.
The Discharge Pipe:

* Must not be smaller in size than the outlet pipe size of

the vaive, or have any reducing couplings or other
restriction.

* Must not be plugged or blocked.
* Must be of material listed for hot water distribution,
* Must be installed so as to allow complete drainage of

both the temperature-pressure relief valve, and the dis­
charge pipe.

* Must terminate at an adequate drain.
* Must not have any vaive between the relief valve and

AWARNING

The temperature-pressure relief valve must be manually
operated at least once a year. Caution should be taken to
ensure that (I) no one is in front of or around the outlet
of the temperature-pressure relief valve discharge line,
and (2) the water manually discharged will not cause any
bodily injury or property damage because the water may
be extremely hot
If after manually operating the valve, it fails to completely
reset and continues to release water, immediately, close
the cold water inlet to the water beater, follow the drain­
ing instructions, and replace the temperature-pressure

relief valve with a new one.

DISCHARtSe PIP6

(Di> cap or piu|f)

Уш btaljurtsdsülwal шдЬогйу,

Ihe d a

№( Valva œn^ng

Ш

ANS

¿2\

,22 йгй ASMS,

ту

э

diefad Irom

хЫ

Stimlshsi wsthlha ìisaifif.

C«i^

2

f

№8

wiEh sudi beai

misi Ise saiMed by she InsfàiïGf ш

of the

шт

wi8i

a locally prescribed Tsmperaiuie-f^ressuis Rdiet Vdv6 lnsìaSetì

in

die

opsorng In

Ш mm

TfiP HEUEF
VALVE PROBE
MUST EXTEND

f^rrQTA^ЗK

TANK г ;

'¡\

TANK

¿ÿii

FiTTING

JFi

BRASS

^

NIPPLE

T4P

SHANK

tENSTH

• If a short

shank {less

llwi

?*) iGroporalLfre-pmssurB

je

II

b

I

vaive

is

lo ba

Inslaflad

las shown), a

nipple end cotiding must

be

used

f{ a

long shank

{2* or loi^sr) is fo to

Instalisif, do

fwf use

fhs nipple

and coupling.

'liisIÉI Tcmi^muire-PfcssuFe

equipinenl requìrad by codes, bu! rtd fóss

Шап

b combina'

lion TempeEalEife-Pisssu/B Raliol Valve certifiMf as moaling Iha ieqdiamSRts fot RelìeI VBhffiS arid
AtSoipaiic QasSiHfloli Devices lof Hd-Waier Supj^y Syslems, ANS 221.22 by a faiìùnailyfecogffeed lesi-
lag laboialory ^al nsaBiìdrre peiìedJs laspectìan oi pfodutiion d llstsd equlpniSRi or maisdals. TìiB valve
musi ¿0 pfianisd, pfo^inJ w!h itidng, or othErwfso InsiaHed so Ihal dischai^ cafi йхЙ

wìdiifi

5 IfiCftss

or al any dstan&e boknv tha sbudural Hoor, ami cannai confaci any Uva еЫг1сг1 pad.*

Por sda operdbn oi Ibe water Iwaler, tfis Relig} Valva

япей

noi

ba reniowid or

Sea rranuai heading - ■^Temj^faiure-Pisssura Rdi&f Valva* ier inslallallon ano mfilnlDnancB of RelieJ

Valve, discharga pif® dher saieiy piscairtloRs.