beautypg.com

Inovonics EE4200 User Manual

Ee4200 echostream, Serial receiver, 2 inovonics wireless contact information

background image

© Inovonics, 2010 - www.inovonics.com

EE4200 EchoStream

®

Serial Receiver

Installation Instructions - 05161D

1 Overview

The serial receiver is a gateway that uses reliable frequency-hopping, spread-
spectrum technology to decode radio frequency (RF) transmissions from end devices
and high-power repeaters, then outputs the decoded data to the application controller
in a common serial data format.

2 Inovonics Wireless Contact Information

If you have any problems with this procedure, contact Inovonics technical support:

E-mail: [email protected]

Phone: (303) 939-9336

3 Connect the Serial Cable

Caution: Long cable runs should not be adjacent to high current power feeds. Keep
cable lengths as short as possible to minimize noise pickup. Measure voltage at the
serial receiver on long cable runs.

1.

Use a small screwdriver to press the housing release tab (Fig. 1A); separate the
housing.

2.

Connect a serial cable to either the serial data port (Fig. 1B) or the serial data
terminal (Fig. 1C). Cabling should meet the following specifications:

Cable requirements 4-conductor 20AWG (or larger) stranded-tinned copper with
PVC insulation rated to 300 volts at 26°C (80°F). (Belden #8205, for example.)
Maximum cable length 30.5 meters (100 feet).
3.

Route the cabling through either the bottom cabling knockout (Fig. 1D) or the side
cabling knockout (Fig. 1E).

4 Mount the Serial Receiver

Caution: Mount the serial receiver in a location removed from metal. Metal objects
(duct work, wire mesh screens, boxes) will reduce RF range.

1.

Use the provided anchors and screws to mount the serial receiver in a location
accessible for future maintenance.

2.

Close the serial receiver housing.

5 Enable EchoStream Select

To meet ETSI requirements, Inovonics has developed a new line of EE 868MHz-only
products. These new 868MHz-only products are compatible with older systems that
include EchoStream select products. If you are using any ES products in your current
system, you will need to enable EchoStream select compatibility on this new 868MHz-
only product.
To enable/disable EchoStream select compatibility:
1.

To enable compatibility with ES products, place a selection jumper on the enable
EchoStream selection pins (Fig. 1).

2.

If no ES products are used in your system, remove the selection jumper from the
EchoStream selection pins (Fig. 1).

6 Grade 2 Requirements

To meet European Grade 2 requirements, the following procedures must be
performed:

6.1 Secure the Housing

There are two screw tabs on the bottom of the housing and one screw tab on the top;
all three must be used to secure the housing.
To secure the housing:
1.

Open the housing

2.

Drill out the three screw holes on the housing base: two on the bottom of the
housing, one on the top.

3.

Use the three 6 x 1/4 screws included in your accessory pack to secure the
housing.

6.2 Cover the Indicator Lights

The indicator lights must be disabled, so that operation cannot be determined
externally.
To cover the indicator lights:
1.

Open the housing.

2.

Apply black electrical tape over the light-holes on the inside of the housing.

3.

Close the housing.

7 Serial Receiver Operation

Caution: The EchoStream system should be tested regularly to ensure operation. To
test, place the system in test mode, activate an end device, and ensure an appropriate
response.

The following LEDs are used to monitor serial receiver operation:
Transmit LED Lit when the serial receiver is transmitting data to the application
controller (Fig. 1F).
Receive LED Lit when the serial receiver is receiving data from the application
controller (Fig. 1G).

Decode LED Lit when the serial receiver is decoding an RF transmission from
another Inovonics Wireless device (Fig. 1H).

8 Specifications

Housing dimensions: 6.38" x 3.60" x 1.10"(162.0 mm x 91.4 mm x 27.9 mm)
Weight: 133 g (4.7 oz)
Power requirement: 10-14 VDC at 100mA
Radio: Inovonics Wireless EchoStream
Operating frequency: 868-869 MHz
Operating environment: -10° to 60°C, (14° to 140°F) up to 90% relative humidity
(non-condensing)
Tamper: Type B, fixed device
Compliance: EN150131-1 Security Grade 2; Environmental Class II
Certification: Telefication B.V.

Figure 1 Serial Receiver components

9 Warranty and Disclaimer

Inovonics Wireless Corporation ("Inovonics") warrants its products ("Product" or
"Products") to conform to its own specifications and to be free of defects in materials
and workmanship under normal use for a period of 36 months from the date of
manufacture. Within the warranty period, Inovonics will repair or replace, at its option,
all or any part of the warranted Product. Inovonics will not be responsible for
dismantling and/or reinstallation charges. To exercise the warranty, the User ("User",
"Installer" or "Consumer") must work directly through their authorized distributor who
will be given a Return Material Authorization ("RMA") Number by Inovonics. Details of
shipment will be arranged directly through the authorized distributor.
This warranty is void in cases of improper installation, misuse, failure to follow
installation and operating instructions, alteration, accident or tampering, and repair by
anyone other than Inovonics.
This warranty is exclusive and expressly in lieu of all other warranties, obligations or
liabilities, whether written, oral, express, or implied. There is no warranty by Inovonics
that Inovonics product will be merchantable or fit for any particular purpose, nor is
there any other warranty, expressed or implied, except as such is expressly set forth
herein. In no event shall Inovonics be liable for an incidental, consequential, indirect,
special, or exemplary damages, including but not limited to loss of profit, revenue or
contract, loss of use, cost of down time, or interruption of business, nor any claim
made by distributor's customers or any other person or entity.
This warranty will not be modified or extended. Inovonics does not authorize any
person to act on its behalf to modify or extend this warranty. This warranty will apply
only to Inovonics Products. Inovonics will not be liable for any direct, incidental or
consequential damage or loss whatsoever, caused by the malfunction of Product due
to products, accessories, or attachments of other manufacturers, including batteries,
used in conjunction with Inovonics Products.
E-mail [email protected] for a copy of the CE Declaration of Conformity.

A Housing release tab

B Serial data port

C Serial data terminal

D Bottom cabling knockout

E Side cabling knockout

F Transmit LED

G Receive LED

H Decode LED

I

Reset button

J Enable EchoStream selection pins

E

D

B

C

F

G

H

A

I

J