3 | areas of application – GEA Bock FK40 User Manual

Page 8

background image

8

09716-10.2013-DGbFEIT

rCn

D
GB
F
E
I
TR
CN

ATTENTION Compressor operation is possible within the limits of application

shown in the diagrams. Please note the significance of the shaded
areas. The limits of application must be observed. Thresholds
should not be selected as design or continuous operating points.

- Max. permissible discharge end temperature: 140°C
- Max. permissible ambient temperature: 100°C
- Max. permissible switching frequency: 12 x /h
- A minimum running time of 2 min. at equilibrium (continuous

operation) must be achieved.

Avoid continuous operation near the threshold. Should the com-

pressor happen to be used near the thresholds, we recommend the
use of a thermal protection thermostat (Accessories, Chap. 7).

When capacity regulators are used, the limits of application can

move.

When operating in the vacuum range, there is a danger of air en-

tering on the suction side. This can cause chemical reactions, a
pressure rise in the condenser and an elevated compressed-gas
temperature. Prevent the ingress of air at all costs!

3| Areas of application

The compressors are factory-filled with the following oil type:

- for R134a, R404A/R507, R407C

FUCHS Reniso Triton SE 55

- for R22

FUCHS Reniso SP 46

Compressors with ester oil charge (FUCHS Reniso Triton SE 55) are marked with an X in the type
designation (e.g. FK

X40/655 N).

3.1 Refrigerants
• HFKW / HFC:

R134a, R404A/R507, R407C

• (H)FCKW / (H)CFC:

R22

3.2 Oil charge

3.3 Limits of application

INFO

For recharging, we recommend the above oil types. Alternatives are:
see lubricants table, Chapter 6.5.