4 | compressor assembly – GEA Bock FK40 User Manual
Page 11
11
09716-10.2013-DGbFEIT
rCn
D
GB
F
E
I
TR
CN
A
A
a
a
A
A
a
a
4| Compressor assembly
4.1 Setting up
4.2 Maximum permissible inclination
A
max. 30°,
max. 2 minutes
a
max. 15°,
continuous
operation
Fig. 8
Fig. 9
Transport and suspension unit on the eyebolt (Fig . 8) or direct on the discharge line valve
(Fig. 9).
Fittings (e.g. pipe holders, additional units etc.) on the compressor are permissible only
following consultation with Bock.
Setup on an even surface or frame with sufficient load-bearing capacity. Use all 4 fastening
points.
Correct setup of the compressor and mounting of the belt drive are decisive for running comfort,
operating safety and the service life of the compressor.
Fig. 10
INFO
New compressors are factory-filled with inert gas (3 bar nitrogen).
Leave this service charge in the compressor for as long as possible
and prevent the ingress of air.
Check the compressor for transport damage before starting any
work.
ATTENTION Poor lubrication can damage the compressor. Respect the stated
values.
WARNING
Move compressors only with hoists that have adequate load-bear-
ing capacity.