6 | commissioning – GEA Bock HG44e User Manual

Page 26

background image

26

D
GB
F
E

96280-12.2014-DGbFEIRu

6| Commissioning

Make sure that the suction and pressure line shut-off valves are open.
With the compressor switched off, add the liquid refrigerant directly to the condenser or receiver,

breaking the vacuum.

If the refrigerant needs topping up after starting the compressor, it can be topped up in vapour

form on the suction side, or, taking suitable precautions, also in liquid form at the inlet to the
evaporator.

6.5 Refrigerant charge

CAUTION

Wear personal protective clothing such as goggles and protective
gloves!

ATTENTION

Avoid overfilling the system with refrigerant!

To avoid shifts in concentration, zeotropic refrigerant blends must
always only be filled into the refrigerating plant in liquid form.

Do not pour liquid coolant through the suction line valve on

the compressor.

It is not permissible to mix additives with the oil and

refrigerant.

6.7 Avoiding slugging

To prevent slugging:

The complete refrigeration system must be properly designed.
All components must be compatibly rated with each other with regard to output

(particularly the evaporator and expansion valves).

Suction gas superheat at the compressor input

should be min. 7 - 10 K. (check the setting

of the expansion valve).

The system must reach a state of equilibrium.
Particularly in critical systems (e.g. several evaporator points), measures are recommended such

as replacement of liquid traps, solenoid valve in the liquid line, etc.
There should be no movement of coolant whatsoever while the compressor is at a standstill.

ATTENTION Slugging can damage the compressor and cause refrigerant to

leak.

6.6 Start-up

Check that the safety and protection devices (pressure switch, motor protection, electrical

contact protection measures, etc.) are all functioning properly.

Switch on the compressor and allow to run for a minimum of 10 min.

Check the oil level by: The oil must be visible in the sightglass.

WARNING

Ensure that both shut-off valves are open before starting the
compressor!

ATTENTION If larger quantities of oil have to be topped up, there is a risk of

oil hammer effects.
If this is the case check the oil return!