beautypg.com

Cooper Lighting Metalux 140 User Manual

Page 2

background image

Metalux • Customer First Center • 1121 Highway 74 South • Peachtree City, GA 30269 • TEL 770.486.4800 • FAX 770.486.4801

12/11/2007 7:51:43 AM

Specifications and Dimensions subject to change without notice.

ADF020715

ORDERING INFORMATION

PHOTOMETRICS

ACCESSORIES

SHIPPING INFORMATION

STN

S A M P L E N U M B E R : S T N - 2 3 2 - 1 2 0 V- E B 8 1- U

Number of Lamps
1
or 2 lamps

(Not Included)

Wattage (Length)
40
=34/40W T12 (48")
32=32W T8 (48")

Voltage

(1)

120V=120 Volt

277V=277 Volt

347V=347 Volt

UNV=Universal

Voltage 120-277

(2)

Blank=4' Length
8T=8' Length

STN=Series

Options
GL
=Single Element Fuse
GM=Double Element Fuse
Emergency=EM Installed

Options

RIF1=Radio Interference

Suppressor

6-3/18 SJT-C&P-515P=Cord

& Plug (120V)

6-3/18 SJT-C&P-L715P=

Cord & Plug (277V)

PI/CPI=Plug-In Option

L715P=Cord & Plug (277V)

TILW=Tandem In-Line

Wiring Option (Consult

TILW Option Catalog Page)

(See options & accessories)

Packaging
U
=Unit Pack
4B=4 Bulk

Ballast Type

(1)

EB8 =T8 Electronic Instant Start.

Total Harmonic Distortion < 10%

EB8 /PLUS=T8 Electronic Instant Start.

High Ballast Factor >1.13. Total

Harmonic Distortion < 20%

ER8 =T8 Electronic Program Rapid Start.

Total Harmonic Distortion < 10%

EB2 =T12 Electronic Rapid Start.

DLS=Digital Lighting System Dimming

No. of Ballast

1, 2 or 3

No. of

Ballast

1, 2 or 3

No. of Ballast

1 or 2

No. of Ballast

1 or 2

C a n d e l a

Angle

Along II

45

o

Across

0

10
20
30
40
50
60
70
80
90

100
110
120
130
140
150
160
170
180

1009

1009

1009

996

1001

1009

942

979

1014

853

945

1026

735

898

1008

593

823

959

432

721

906

260

633

824

100

460

600

9

248

381

7

336

527

7

255

448

7

211

364

7

142

276

7

76

175

7

18

79

7

5

5

0

0

0

0

0

0

C o e f f i c i e n t s o f U t i l i z a t i o n

Effective floor cavity reflectance

20%

rc

80%

70%

50%

30%

10%

0%

rw

70 50 30 10

70 50 30 10

50 30 10

50 30 10

50 30 10

0

RCR

0
1
2
3
4
5
6
7
8
9

10

Z o n a l L u m e n S u m m a r y

Zone

Lumens

%Lamp

%Fixture

0-30
0-40
0-60
0-90
90-180
0-180

||

STN-232

Electronic Ballast
F32T8/35K Lamps

2850 Lumens
Spacing criterion:

(II) 1.3 x mounting

height, (

⊥) 1.5 x

mounting height
Efficiency 93.5%
Test Report:

STN232.IES
LER = FS-80
Yearly Cost of 1000

lumens, 3000 hrs at

.08 KWH = $3.00

822

14.4

15.4

1397

24.5

26.2

2724

47.8

51.1

4250

74.6

79.8

1078

18.9

20.2

5328

93.5

100.0

107 107 107 107

102 102 102 102

93 93 93

85 85 85

78 78 78

75

95 90 86 81

91 86 82 78

79 75 72

72 69 67

65 63 61

58

86 77 70 64

81 74 67 62

67 62 58

61 57 53

56 53 50

46

78 67 59 52

74 64 57 51

59 53 47

54 49 44

49 45 41

38

71 59 50 44

67 56 48 42

52 45 40

47 42 37

43 38 35

32

64 52 43 36

61 49 41 35

45 38 33

41 35 31

38 33 29

26

59 46 37 31

56 44 36 30

40 33 28

37 31 26

34 29 25

22

54 41 32 26

51 39 31 26

36 29 24

33 27 23

30 25 21

19

50 37 28 23

47 35 27 22

32 26 21

30 24 19

27 22 18

16

46 33 25 19

43 31 24 19

29 22 18

27 21 17

24 19 16

14

43 30 22 17

40 29 21 17

26 20 16

24 19 15

22 17 14

12

(Order Separately)

A1B=Spacer
GRP-STN=Gripper Hanger (Use 2 Per Fixture)
AYC-Chain/Set=36" Chain Hanger (Use 1 Set Per Fixture)
SCF=Fixed Stem Set (Specify Length)
SCS=Swivel Stem Set (Specify Length)
ATG-4=Tong Hanger (Use 2 Per Fixture)
DI2=Long Connector
STN/SS-ASY-3

(3)

=3" Asymmetric Reflector (Specify 2', 3', or 4')

STN/SS-ASY/REV-3

(3)

=3" Asymmetric Reverse Reflector

(Specify 2', 3', or 4')

STN/SS-SYM-6

(3)

=6" Symmetric Reflector (Specify 2', 3', or 4')

STN/SS-ASY-6

(3)

=6" Asymmetric Reflector (Specify 2', 3', or 4')

IC-4FT-REFL

(3)

=12" Symmetric Reflector

WG/SS-4FT=Wire Guard

(Additional Accessories Available. See Options and Accessories Section.)

STN-132

12 lbs.

8TSTN-132

20 lbs.

STN-232

12 lbs.

8TSTN-232

24 lbs.

Catalog No.

Wt.

This manual is related to the following products: