beautypg.com

Long-distancewireruns, Maximum one-way distance and wire size – Windy Nation Xantrex C Series Multifunction DC Controller User Manual

Page 62

background image

Installation

42

975-0004-01-02 Rev D

Long-distance wire runs

If there is a significant distance between the PV array and the
controller and/or the controller and the battery, larger wires
can be used to reduce the voltage drop and improve
performance. Refer to

Table 2-4

.

To use a larger size wire, use a splicer block (terminal block)
intended for this purpose. This allows the larger cable size
from the batteries to be “spliced” to the smaller wire size
connected to the controller. Split-bolt kerneys can also be
used for wire splices.

Follow manufactures recommendations for torque and
mounting (if required). Splicer blocks and split-bolt kerneys
are available from renewable energy suppliers.

Maximum One-way Distance and Wire Size

Refer to

Table 2-4

and find your maximum current in the left

column, and the one-way distance from your power source
(feet/meters) to the

C-Series controller

(or the distance from

the

C-Series controller

to your load) on the same line, then

read the wire size required at the top of the column.

Important:

NEC Article 690 and local electrical codes should

be consulted for wire sizing and any additional installation
requirements.

For a C60 use a 60 amp, 100% Continuous Duty breaker and
#6 AWG, 90 °C wire.

Larger wire sizes may be used to improve performance, but
are NOT approved by UL to be installed in the controller. Use
a splicer block as previously described.