beautypg.com

Troubleshooting information, Cont'd) – Steffes DLF40B User Manual

Page 31

background image

Troubleshooting Information

(cont'd)

30 

B.    PROBLEM:    FURNACE  WILL  NOT  DELIVER  HEAT 

With room thermostat call for heat, check 

LED's on charge control circuit board panel 

(30).  "POWER ON" & "HEAT CALL" lights 

must both be ON. 

Jumper room thermostat 

connections  "R" and "W" 

terminal block positions 

on the charge control circuit 

board (30). 

Lights Off 

Check for core blower 

motor (38) operation. 

Lights On 

Repair room thermostat 

or field wiring. 

Check for 24 VAC between 

room thermostat connection 

"C" terminal block position and 

the two 3­amp low voltage 

fuses on the charge control 

circuit board (30). 

Check core blower relay 

operation (34). (Top relay in 

furnace electrical panel.) 

Check wire connections below 

charge control circuit 

board (30) and/or change the 

charge control circuit 

board (30). 

Check unit wiring 

and/or replace 

defective control 

transformer (28). 

Check heat exchanger and 
core blower limit switches 

(27 & 53) & core blower 

speed switch (69). 

Check core blower 

relay coil voltage 

for 24 VAC. 

Core Blower Runs 

Core Blower 

Does Not Run 

Core Blower 

Does Not Run 

Ok 

Inoperable 

Replace defective 

switch(es). 

Check core blower 

motor (38) & unit wiring. 

Replace core 

blower relay (34). 

Replace charge 

control circuit 

board (30). 

Ok 

No Voltage 

Ok 

Defective 

Remove supply air plenum cover.  Check heat exchanger 

temperature should be 135ºF minimum with core blower running. 

Ok 

No Voltage 

Core Blower 

Runs 

Low or no core 

charge or core 

blower wheel 

(36) problem. 

No Heat 

Check for contact closure on supply air blower switch (52). 

Check supply air blower limit (54), core blower motor (38), & voltage 

between blue & blue/red wires on supply air blower motor (58) supply cable. 

(NOTE:  In heating mode the supply air blower motor (58) runs on the 

normally closed relay contact.  Relay is not pulled in for heating.) 

Replace supply air 

blower switch (52). 

Will Not Close 

Ok 

Ok

This manual is related to the following products: