beautypg.com

Steffes 612EXT Owner & Installers Manual User Manual

Page 27

background image

Unit charges improperly.

UNIT

CHARGES

UNEVENLY

Check unit amperage.

Check heating elements (54) and charge

control sequencer (49) for proper operation.

Check fans (53) and dampers for

smooth operation.

DEFECTIVE

Repair fan/damper system.

UNIT
UNDERCHARGES

LESS THAN
RATED
AMPERAGE

OK

RATED

AMPERAGE

Check voltage between A1 and A2

terminal block positions (24).

Check for line voltage between L2

and T2 terminal block positions

(24), or observe service light for

illumination.

VOLTAGE
PRESENT

Troubleshoot and repair load man-
agement control, automatic charge

control system or field wiring.

Replace charge

control thermostat (45).

NO
VOLTAGE
PRESENT

NO

VOLTAGE

PRESENT

(Service light off.)

VOLTAGE
PRESENT
(Service
light on.)

UNIT
OVERCHARGES
(With manual
Charge Control.)

Replace core

charging high

limit switch

(33).

Check unit wiring. If correct,

replace charge control

thermostat (45).

Model: S Series Only

Function: Core Charging

Problem: Improper Charging

Before starting any procedures listed below, check room thermostat and circuit breaker settings.

Note: For cross reference to number coded components, see figure 7.