Features – Beckett 7505 User Manual
Page 2
2
Table 1 - Models and Cross Reference Guide
Beckett GeniSys
Control Part No.
Lockout
Time
Valve-on
delay time
2
Motor-off
delay time
2
Replaces
Honeywell:
Replaces
Carlin:
7505A 0000
15 sec
-
-
R7184A, R8184G
48245, 40200,
42230, 50200
1
7505B 1500
15 sec
15 sec
-
R7184B
-
7505P 1515
15 sec
15 sec
15 sec
R7184P, R7184U
1
60200
1
7505P 1530
15 sec
15 sec
30 sec
R7184P, R7184U
1
60200
1
7505P 152M
15 sec
15 sec
2 min
R7184P, R7184U
1
60200
1
1 - Beckett snap-on alarm module required for direct replacement of this control.
2 - Valve-on delay and motor-off delay timings on all models are programmable with Beckett snap-on
programming display. Other factory set timings are available. Contact Beckett for alternate timings.
Features
Thermostat / Operating (if applicable) and Limit Control Compatible
Welded Relay Protection
Limited Recycle
Limited Reset
3 Status Lights
Valve-On Delay / Motor-Off Delay (Field programmable with Beckett add-on Display)
15 Second Lockout Time
Interrupted or Intermittent Duty Ignition
Technician Pump Priming Mode
Disable Function
Communication Ports (2)
◦
◦
◦
◦
◦
◦
◦
◦
◦
◦
◦