beautypg.com

Maintenance, Disable function – Beckett 7505 User Manual

Page 11

background image

11

120v GeniSys Control Installation and Operation Manual

automatically return to standby mode.

If prime is not established during the
four minute pump prime mode, return
to step 5 to re-enter Pump Prime
mode. Repeat steps 5 through 7
until the pump is fully primed and the
oil is free of bubbles.

Terminate the call for heat, and the
control will resume normal operation.

Cad Cell Resistance Measurement

If the Beckett 7505 control is equipped
with the GeniSys Display Module, part
52067U, the cad cell resistance can be
selected and read on the LCD screen.
Also, the GeniSys Contractor Tool, part
52082U, can be used for this purpose.

If these are not available, the cad cell
leads can be unplugged from the control
and the resistance measured with a
meter in the conventional way.
Conduct these tests with fl ame present.

Flame Detection Range

Normal (0 - 1600 ohms)

Limited (1600 ohms to lockout)

Resetting From Restricted or
Hard Lockout

8.

9.

Maintenance

Oil heating systems require annual
service performed by a qualifi ed,
professional service agency. The 7505
primary control should be inspected
during this service routine according to
the following checklist:

NOTE: The 7505 control has no

serviceable internal parts. Do not

attempt to remove cover.
Inspect the exterior of the control.

Replace the control if there is any

sign of impact damage, water or

corrosion.
Use a multimeter to test the line

voltage at control L1 and L2. It

should be 102 - 132 Vac.
Inspect all external wiring for secure

connections and verify insulation

integrity.
Verify the control lockout and

operation sequence, (Reference

Startup/Checkout section).
Observe a full operating cycle to

prove the sequence and timings are

correct.
Replace any control that does not

meet listed specifi cations with an

equivalent replacement unit.

Before starting or resetting the

control from restricted lockout

state, troubleshoot the heating

system for the root cause(s) of

the lockout.

Fire & Smoke
Hazard

Make necessary repairs or adjustment to

ensure a safe start condition.
Ensure that the appliance is free of oil and oil

vapors before starting or resetting the burner.

to limit accumulation of unburned oil in
the combustion chamber.
To reset, hold the button down for 15
seconds until the red light turns off and
the yellow light turns on.
Always verify the control functions
according to all specifi cations before
leaving the installation site.
Replace the control if it does not
operate as specifi ed.

Disable Function

Any time the burner is running, press
and hold the reset button to disable the
burner. The burner will remain off as
long as the button is held.

If the control continues to lock out
without a satisfi ed call for heat, or
fails the motor relay check, the control
enters Hard (restricted) Lockout in order