2. Hints

2.3 How to adjust parameters

RWF40 user manual Section 6.3


Shown at the right is the basic display.

The current configuration of your specific

controller will determine which levels you will be
allowed to access.

C112 must be xxx1 or xxx0 to access the parameter
level.

The C112 locking code can only be adjusted by the manufacturer.



From the basic display, you may skip the user level, to reach the
parameter level.

Press

and hold, for 3 seconds, and release.


The actual value display, (

0

)

shows the current parameter value.

The setpoint display, (

AL

)

shows the parameter item you are adjusting.



Parameter level items summary:

AL A

larm

L

imit value for comparator

HYSt

Switching differential,

Hyst

eresis for limit comparator

Pb.1 P

roportional

b

and

1

dt d

erivative

t

ime

rt

Integ

r

al action

t

ime

db

*

d

ead

b

and, contact spacing

tt

* Ac

t

uator running

t

ime

HYS1

Switch-on threshold,

Hyst

eresis

1

, 2-stage burner

HYS2

Switch-off threshold,

Hyst

eresis

2

, 2-stage burner

HYS3

Switch-off threshold,

Hyst

eresis

3

, upper

q

Response threshold

H H

eating curve slope

P P

arallel displacement


* Items are only displayed when controller

is configured for a 3-position output.

Example Adjust the value for parameter AL.



If no keys are pressed for 30 seconds, at anytime, the controller will

automatically return to the basic display.


The current value of AL, (

0

)

is shown in the actual value display.

The current parameter item (

AL

)

is shown in the setpoint display.

The display is steady, (nothing is flashing)
and the value for AL can now be adjusted.






You can decrease

You can increase

the value by

the value by

pressing

pressing

and releasing it.

and releasing it.







You can accept

Or, you can

the change by

advance to the

waiting 2 seconds.

Next parameter

by pressing

once and

The red LED’s will

releasing it.

blink once, and
become the new

HYSt can be

value. adjusted

the

same way you

just did AL.





Your options at this point are:

Press

and release

,

to immediately return to the basic display.


Press

and release it, to advance down to Pb.1,

(the next parameter).

… after the last parameter item P, press

and release it,

to advance down to SP1, (the 1

st

user item).


… after the last user item, the menu cycles back to the 1

st

user item.


Or simply wait 30 seconds and the controller will automatically return to
the basic display.