• A maximum of 24 Kidde Safety devices may be interconnected

in a multiple station arrangement. The interconnect system
should not exceed the NFPA interconnect limit of 12 smoke
alarms and/or 18 alarms total (smoke, CO, Smoke/ CO
Combination, heat, etc.). This Smoke/CO combination alarm
must be counted as a smoke alarm when determining the
number of units on an interconnect line. With 18 alarms
interconnected, it is still possible to interconnect up to a total
of 6 remote signaling devices and /or relay modules (see page
15 for details on interconnecting Kidde devices).

• The maximum wire run distance between the first and last unit

in an interconnected system is 1000 feet.

• Figure 3 illustrates interconnection wiring.

Improper

connection will result in damage to the alarm, failure to
operate, or a shock hazard.

• Make certain alarms are wired to a continuous (non-switched)

power line. NOTE: Use standard UL Listed household wire (as
required by local codes) available at all electrical supply stores
and most hardware stores.

Installation Instructions

12

FUSE OR CIRCUIT BREAKER

RED

BLACK

WHITE

CONNECTOR

RED

BLACK

WHITE

CONNECTOR

First
Alarm

Additional
Alarm

Kidde

Relay Module

SM120X

Additional
Alarm

Optional

Accessory

WIRES ON ALARM HARNESS

CONNECTED TO

Black

Hot Side of AC Line

White

Neutral Side of AC Line

Red

Interconnect Lines (Red Wires) of
Other Units in the Multiple Station
Set up

FIGURE 3 Interconnect Wiring Diagram

2544-7201-01(KN-COSM-IBA)_V2.qxd:_ 2014.5.29 4:35 PM Page 14