• A maximum of 24 Kidde Safety devices may be interconnected
in a multiple station arrangement. The interconnect system
should not exceed the NFPA interconnect limit of 12 smoke
alarms and/or 18 alarms total (smoke, CO, Smoke/ CO
Combination, heat, etc.). This Smoke/CO combination alarm
must be counted as a smoke alarm when determining the
number of units on an interconnect line. With 18 alarms
interconnected, it is still possible to interconnect up to a total
of 6 remote signaling devices and /or relay modules (see page
15 for details on interconnecting Kidde devices).
• The maximum wire run distance between the first and last unit
in an interconnected system is 1000 feet.
• Figure 3 illustrates interconnection wiring.
Improper
connection will result in damage to the alarm, failure to
operate, or a shock hazard.
• Make certain alarms are wired to a continuous (non-switched)
power line. NOTE: Use standard UL Listed household wire (as
required by local codes) available at all electrical supply stores
and most hardware stores.
Installation Instructions
12
FUSE OR CIRCUIT BREAKER
RED
BLACK
WHITE
CONNECTOR
RED
BLACK
WHITE
CONNECTOR
First
Alarm
Additional
Alarm
Kidde
Relay Module
SM120X
Additional
Alarm
Optional
Accessory
WIRES ON ALARM HARNESS
CONNECTED TO
Black
Hot Side of AC Line
White
Neutral Side of AC Line
Red
Interconnect Lines (Red Wires) of
Other Units in the Multiple Station
Set up
FIGURE 3 Interconnect Wiring Diagram
2544-7201-01(KN-COSM-IBA)_V2.qxd:_ 2014.5.29 4:35 PM Page 14