Air Filter(s) —

Air filter(s) should be checked monthly

and changed when necessary. Units may have either 2-in. or

4-in. thick filters. For units with 2-in. thick filters, all filters will

be 20 x 24 x 2-in. size. For units with 4-in. thick filters, half the

filters will be 20 x 24 x 4-in. size and half will be 20 x 20 x

4-in. size. The filter access panel is located at the end of the unit

opposite of the condenser section. The access door is labeled to

indicate that it is the filter access door.
To replace or inspect filters:

1. Loosen the 3 latches securing the filter access door and

open door.

2. Remove the bolt securing the inner access panel, located

behind the filter access door, using care not to lose the

bolt.

3. Remove the inner access panel.

4. Slide the black plastic filter retainer towards you and

remove.

5. Remove filters by pulling toward you and away from the

filter track.

6. A filter removal rod is shipped taped to the partition

located near the bottom filter track. The filter removal rod

will aid in the removal of filters beyond the reach of the

service person.

7. Inspect or replace filters.
8. Return filters to filter tracks. Note direction of airflow

arrows on filter frame.

9. Reinstall the black plastic filter retainer.

10. Place the filter removal rod back on the partition for

future use.

11. Reinstall inner panel.

12. Reinstall bolt securing the inner panel.
13. Close filter access panel and tighten latches.

If you have difficulty in locating your air filter or if you

have questions concerning proper filter maintenance, contact

your dealer for instructions. When replacing your unit filters,

always use the same size and type of filter that was originally

supplied by the installer.

Units with outdoor air capability have a cleanable filter for

the outdoor air. This filter should be checked annually and

cleaned as necessary with steam or hot water and a mild deter-

gent. Do not use throwaway filters in place of cleanable filters.

Heat Exchanger —

To ensure dependable and efficient

heating operation, the heat exchanger should be checked by a

qualified maintenance person before each heating season and

cleaned when necessary. This checkout should not be attempt-

ed by anyone not having the required expertise and equipment

to do the job properly. Checking and/or cleaning the heat

exchanger involves removing the gas controls assembly, the

flue collector box, and the flue collector box cover. When

finished, the gas controls assembly must be reinstalled for

proper operation. Also, the flue collector box cover must be

replaced correctly so that a proper seal is maintained. Refer to

unit installation instructions for correct procedure. Contact

your dealer for the required periodic maintenance.

Fans and Belts —

Periodically check the condition of

the fan wheels and housings, and belt tension. When service is

necessary, call your dealer.

Indoor-Fan Motor, Outdoor-Fan Motor, and
Combustion Fan Motor —

Lubrication is not recom-

mended. Bearings will not require lubrication for at least

5 years of normal operation. After 5 years, motor life can be

extended by having the motors serviced at an authorized motor

service shop.

Fan Shaft Bearings —

The bearings should be greased

with Shell Alvania no. 2 grease or equivalent. The bearings

will need to be greased annually, dependent on fan usage. Do

not grease more than once a year.

Evaporator and Condenser Coils —

Cleaning of

the coils should be done by qualified service personnel.

Contact your dealer for the required annual maintenance.

Condensate Drain —

The drain pan and condensate

drain line should be checked and cleaned at the same time the

cooling coils are checked by your dealer.

Compressor —

All compressors are factory supplied with

a normal charge of the correct type of refrigeration-grade oil in

them and should not require additional oil.

Condenser Fan

The fan must be kept free of all obstructions to ensure prop-

er cooling. Contact your dealer for any required service.

Electrical Controls and Wiring —

Electrical con-

trols are difficult to check without proper instrumentation. If

there are any discrepancies in the operating cycle, contact your

dealer and request service.

Refrigerant Circuit —

The refrigerant circuit is difficult

to check for leaks without the proper equipment. If inadequate

cooling is suspected, contact your local dealer for service.

Combustion Area and Vent System —

The com-

bustion area and vent system should be visually inspected be-

fore each heating season. The normal accumulation of dirt,

soot, rust, and scale can result in loss of efficiency and im-

proper performance if allowed to build up.

See Fig. 1 and 2 and proceed as follows to inspect the com-

bustion area and power-venting system of your unit.

1. Turn off gas supply to your unit.
2. Turn off electrical power to your unit.
3. Remove gas section access panels.
4. Using a flashlight, carefully inspect the burner areas for

dirt, soot, rust, or scale.

5. When you have completed your inspection, follow the To

Light Unit section in this manual to restore your unit to

operation.

WARNING

Never operate your unit without filters in place. Failure to

heed this warning may result in damage to the blower

motor and/or compressor. An accumulation of dust and lint

on internal parts of your unit can cause loss of efficiency

and, in some cases, fire.

WARNING

Do not poke sticks, screwdrivers, or any other object into

revolving fan blades. Severe bodily injury may result.

CAUTION

If your unit makes any unusual or especially loud noises

during heating, shut down the heating section and call your

dealer.

CAUTION

If dirt, soot, rust, or scale accumulations are found, call

your dealer and do not operate your heating section.