Bradford White U-PDX-75S-55FR-3N User Manual
Page 14
14
Venting continued-
Table 2 lists the venting distances allowed with 4” (10.2 cm) diameter vent pipe.
When venting with 4” (10.2 cm) vent pipe, use a 4” (10.2 cm) to 3” (7.6 cm)
reducer to exit through the building wall with 3” (7.6 cm) vent pipe. Use the 3”
(7.6 cm) vent terminal supplied with the water heater to terminate on the
outside of the building. If the length of 3” (7.6 cm) vent pipe needed to go
through the wall is greater than 14” (35.5 cm), use 4” (10.2 cm) to go through
the wall and reduce to 3” (7.6 cm) vent pipe immediately after exiting the
outside wall. Refer to the venting illustrations on the following pages. Make
sure the vent pipe terminal elbow fitting is at least 1” (2.5 cm) away from the
edge of the wall.
IMPORTANT
The minimum equivalent length for the exhaust portion of the vent is 7
feet. The maximum equivalent vent length for the exhaust is 60 feet for
3” diameter pipe (50 feet for the 75 gal.) and 100 feet for 4” diameter
pipe (90 feet for the 75 gal.). The intake portion of the vent must be
equal to or less than the vent length of the exhaust. The tables below
are provided for your quick reference, some installations may require a
greater number of elbows. When calculating equivalent vent length,
one 90º elbow is equivalent to 5 feet.
TABLE 1 - VENT CONNECTOR LENGTHS
FOR 3” (7.6 cm) DIAMETER VENT PIPE
Terminating
# of Elbows
(excl. vent
term.)
Maximum straight
Length ft (m)
Minimum
straight
Length
ft (m)
48, 65
gal.
75 gal.
Through the Wall
1 55
(16.8) 45
(13.7)
2 (.6)
Through the Wall
2 50
(15.2) 40
(12.2)
2 (.6)
Through the Wall
3 45 (13.7) 35
(10.7)
2 (.6)
Through the Wall
4 40
(12.2) 30
(9.1)
2 (.6)
Through the Roof
0 60
(18.3) 50 (15.2)
7 (2.1)
Through the Roof
1 55
(16.8) 45 (13.7)
7 (2.1)
Through the Roof
2 50 (15.2) 40
(12.2)
7 (2.1)
Through the Roof
3 45 (13.7) 35
(10.7)
7 (2.1)