Led status control status probable cause, Troubleshooting – Bradford White TW4-75S-76B-3N User Manual

Page 36

background image

36

TROUBLESHOOTING

LED Status

Control Status

Probable Cause

None (LED not on or 

flashing) 

Electrical power not 

present. 

Control power switch in “OFF” position.Supply 
voltage interuppted. 

One short flash every 

four seconds 

Stand‐by mode, 

Thermostat is 

satisfied (no faults). 

Temperature demand is satisfied (no call for heat). 

Alternates bright and 

dim (Heartbeat) 

Thermostat calling 

for heat (no fault). 

Tank temperature below set point of thermostat. 

Short flash once 

every second 

Weak pilot signal on 

last call for heat. 

1. Unstable pilot. 
2. Pilot tube block or restricted. 
3. Oxidation build up on pilot electrode. 
4. Wire damage to pilot assembly or bad 
connection 
at gas valve. 

Short flash once 

every two seconds 

Idle remote 

command off 

1. Control put in idle or Sabbath mode from 

accessory module 

Two flashes, three 

second pause 

Pressure switch not 

working‐closed 

position. 

1. Pressure switch tubing kinked or blocked. 
2. Blocked pressure tap on switch. 
3. Faulty pressure switch. 

Three flashes, three 

second pause 

Pressure switch or 

blower temperature 
switch not working ‐

open position. 

1. Vent blockage or improper vent configuration. 
2. Pressure switch tubing kinked or blocked. 
3. Blower not spinning up to speed. 
4. Vent temperature too high 
5. Faulty pressure switch or vent limit switch. 

Four flashes, three 

second pause 

Excessive tank 

temperature. 

System must be 

reset. 

1. Excessive sediment 
2. Hot water entering the tank from another        
  source in the potable loop. 
3. Faulty gas valve. 

Five flashes, three 

second pause 

False pilot flame 

present. 

1. Pilot valve stuck in open position. 

Six flashes‐one flash, 

three second pause 

(Soft lockout) 

Failed to light pilot. 

System auto resets 

after 5 minutes. 

1. Unstable pilot. 
2. Pilot tube blocked or restricted. 
3. Oxidation build up on pilot electrode. 
4. Wire damage to pilot assembly or bad 
connection at gas valve. 

Six flashes‐two 

flashes, three second 

pause (Soft lockout) 

Pressure switch or 

blower temperature 

switch opened 

during burner 

operation. 

System auto resets 

after 5 minutes. 

1. Pressure switch tubing kinked or blocked. 
2. Vent blockage or improper vent configuration. 
3. Vent termination being affected by windy 
conditions. 
4. Blower not spinning up to speed. 
5. Vent temperature too high 
6. Faulty pressure switch or blower temp. switch.