Water Connections
NOTE: BEFORE PROCEEDING WITH THE INSTALLATION, CLOSE THE
MAIN WATER SUPPLY VALVE.
After shutting off the main water supply, open a faucet to relieve the water line
pressure to prevent any water from leaking out of the pipes while making the
water connections to the water heater. After the pressure has been relieved,
close the faucet. The COLD water inlet and HOT water outlet are identified on
the top of the water heater. The fittings at the cold water inlet and hot water
outlet are dielectric waterway fittings with 3/4 inch NPT male thread. Make the
proper plumbing connections between the water heater and the plumbing
system to the house. Install a shut-off valve in the cold water supply line.
CAUTION
If sweat fittings are to be used DO NOT apply heat to the nipples on top of
the water heater. Sweat the tubing to the adapter before fitting the adapter
to the water connections. It is imperative that heat is not applied to the
nipples containing a plastic liner.
If this water heater is installed in a closed water supply system, such as one
having a back-flow preventer in the cold water supply, provisions must be made
to control thermal expansion. DO NOT operate this water heater in a closed
system without provisions for controlling thermal expansion. Your water
supplier or local plumbing inspector should be contacted on how to control this
situation.
After installation of the water lines, open the main water supply valve and fill the
water heater. While the water heater is filling, open several hot water faucets
to allow air to escape from the water system. When a steady stream of water
flows through the faucets, close them and check all water connections for
possible leaks. NEVER OPERATE THE WATER HEATER WITHOUT FIRST
BEING CERTAIN IT IS FILLED WITH WATER.
WARNING
FAILURE TO INSTALL AND MAINTAIN A NEW, LISTED 3/4 inch X 3/4
inch TEMPERATURE AND PRESSURE RELIEF VALVE WILL RELEASE
THE MANUFACTURER FROM ANY CLAIM THAT MIGHT RESULT FROM
EXCESSIVE TEMPERATURE AND PRESSURES.