Venting continued-
TABLE 1 - VENT CONNECTOR LENGTHS
FOR 3 inch (7.6 cm) DIAMETER VENT PIPE
Terminating #
of
Elbows
(excl.
vent
term)
Maximum straight
Length ft (m)
Minimum
straight
Length ft (m)
48, 65 gal.
25, 55 and
75 gal.
Through the Wall
1 55
(16.8) 45 (13.7)
2 (.6)
Through the Wall
2 50
(15.2) 40
(12.2)
2 (.6)
Through the Wall
3 45 (13.7) 35 (10.7)
2 (.6)
Through the Wall
4 40
(12.2) 30 (9.1)
2 (.6)
Through the Roof
0 60
(18.3) 50 (15.2)
7 (2.1)
Through the Roof
1 55
(16.8) 45 (13.7)
7 (2.1)
Through the Roof
2 50 (15.2) 40
(12.2)
7 (2.1)
Through the Roof
3 45 (13.7) 35 (10.7)
7 (2.1)
TABLE 2 -VENT CONNECTOR LENGTHS
FOR 4 inch (10.2 cm) DIAMETER VENT PIPE
Terminating
# of 90
Elbows (excl.
vent term.)
Maximum straight
Length ft (m)
Min
straight
Length
ft (m)
48, 65 gal.
25, 55 and
75 gal.
Through the Wall
1 175 (53.3) 175 (53.3)
10 (3.1)
Through the Wall
2 170 (51.8) 170 (51.8)
10 (3.1)
Through the Wall
3 165 (50.3) 165 (50.3)
10 (3.1)
Through the Wall
4 160 (48.8) 160 (48.8)
10 (3.1)
Through the Wall
5 155 (47.2) 155 (47.2)
10 (3.1)
Through the Roof
0 180 (54.9) 180 (54.9)
15 (4.6)
Through the Roof
1 175 (53.3) 175 (53.3)
15 (4.6)
Through the Roof
2 170 (51.8) 170 (51.8)
15 (4.6)
Through the Roof
3 165 (50.3) 165 (50.3)
15 (4.6)
Through the Roof
4 160 (48.8) 160 (48.8)
15 (4.6)
NOTE: When using 4 inch (10.2 cm) vent pipe, use a 4 inch (10.1 cm) to 3
inch (7.6 cm) reducer and exit the building wall with 3 inch (7.6 cm) vent
pipe using the 3 inch (7.6 cm) 90
vent terminal supplied. Two 45 elbows
are equivalent to one 90
elbow.