Installing pipe clamp around pipe every 3 feet to support pipe.  Install pipe clamps on each side of elbow. 
 

 

 

 
 
 
Steel joint connector rings (available from Centrotherm supplier) must be used at each pipe joint.  The connector rings 
ensure that the joints do not separate under heavy loads.  These connector rings must be used to comply with ULC‐S636 
requirements.  See following photo with the joint connector attached to the pipe sections. 
 
Pipe shown with connector ring  

 

 

 
Step 6:  If any of the straight pipe sections need to be cut, use a hack saw and make a straight cut on the male 
(ungasketed) end of the pipe.  When making the cut, allow for the 2” minimum (51 mm) insertion distance inside the 
female end of the pipe.  Using a razor knife, deburr the edges of the cut pipe to make an approximately 15 degree bevel 
to avoid any sharp edges that may damage the gasket. 

WARNING

Cut pipe edges must be properly deburred. Damage to the gasket from not deburring the edges of the cut male
end may result in the release of dangerous flue products.

 

WARNING

DO NOT operate vent system without properly
installing Connector Rings.

Centrotherm Pipe Hangers – Clamps attach 
to vent pipe. 

Centrotherm Connector Ring.  Hooked 
bracket over bottom joint as shown